I guess this is wrong huh
Mike, It's not perfectly clear in your photo... but, it looks like the top ground
ed conductor is not in the same set-screw as the ground
ing(ground) counductors-- which would make that set up ok.
The grounding (ground) conductors CAN have multiple conductors under teh same set screw but there
should-not be ground
ed conductors (think neutrals) with multi-conductors under the same set-screw. Nor should there be both a ground
ing and ground
ed conductor under the same set screw at that bar.
Clear as mud??