Are the wires sized for 300 amps? The don't look like it.
Are the lugs intended for multiple conductors? I don't think they are.
I can't tell if the 'tap rules' apply, from the information given.
Finally, is that disconnect listed for use as service equipment? I have my doubts ....
|