Re: PVC conduit and outlet installed at service panel
Man oh man! Several things wrong. NO the outlet cut into the service panel is not allowed. They have screwed up the weather proof inegety of the SP. Plus the recept looks like it is not GFCI protected, not even in an approved box for this type of installation.
The PVC is not allowed for this type of installation. The PVC looks like a vent fitting and it is not protected from UV rays.
There is not anything in writing about water lines and electrical conduit being next to each other.
|