I came across a CSST line run through a chimney. The installer wrapped the pipe with some electrical tape before filling the hole with cement around it. Is this an acceptable "cushion"? Thanks in advance.
David Bell
04-25-2011, 08:24 AM
Should be sleeved and correctly fire stopped
Ray Norton
04-25-2011, 09:16 AM
I go directly to the manufacturer when I see suspect installlations such as this one. See Sections 4.3.8 and 4.3.9 for installation requirements (link below). In short: No, eletrical tape is not an adequate alternative to a compliant sleeve. Also, the CSST may not be routed through a chimney chase, IRC G2415.1 prohibits this.