View Full Version : Equipment grounds are bundled together



Sam Morris
09-18-2017, 03:33 PM
Does anyone know if this equipment connector is rated for 20 equipment ground wires (GE panel 1971) ?? Thanks

Jerry Peck
09-18-2017, 03:41 PM
It is not.

It is also not rated for copper and aluminum intermixed.

That is not to say that electrical contractors did 'use what they had on the truck' when they needed to do something - all contractors seen to 'use what they had' when the need arose ... didn't matter if it was right, just "Git R Done".