Results 1 to 9 of 9
  1. #1
    Join Date
    Nov 2015
    Location
    WA
    Posts
    20

    Default Tamper resistent electrical outlets

    I am confused regarding tamper resistant electrical outlets - are they mandatory in new dwelling units now?

    New house was built. I was told that all electrical outlets must be tamper resistant as per code in WA state? Even GFCI has to be tamper resistant?

    Similar Threads:
    Member Benefits1

  2. #2
    Join Date
    Mar 2007
    Location
    Santa Rosa, CA
    Posts
    3,154

    Default Re: Tamper resistent electrical outlets

    Quote Originally Posted by Robert Gaspy View Post
    I am confused regarding tamper resistant electrical outlets - are they mandatory in new dwelling units now? New house was built. I was told that all electrical outlets must be tamper resistant as per code in WA state? Even GFCI has to be tamper resistant?
    Hi Robert,

    I believe the requirement is/was new in the 2014 NEC. I don't know when TR showed up in the IRC. Is WA state enforcing the 2014 NEC? CA starts enforcing it Jan. 1, 2017. Call your local building department to find out what code is currently being enforced.

    As I recall, 210.52 requires TR outlets at most interior and exterior locations, including garages, bathrooms & kitchens. Exceptions are for receptacle outlets for appliances that are generally not moved (my assumption would be dishwashers, refrigerators, etc.). I believe NFPA has a free online access to the code if you don't have one.

    Department of Redundancy Department
    Supreme Emperor of Hyperbole
    http://www.FullCircleInspect.com/

  3. #3
    Join Date
    Sep 2008
    Location
    so so, California
    Posts
    1,867

    Default Re: Tamper resistent electrical outlets

    Quote Originally Posted by Gunnar Alquist View Post
    Hi Robert,

    I believe the requirement is/was new in the 2014 NEC. I don't know when TR showed up in the IRC. Is WA state enforcing the 2014 NEC? CA starts enforcing it Jan. 1, 2017. Call your local building department to find out what code is currently being enforced.

    As I recall, 210.52 requires TR outlets at most interior and exterior locations, including garages, bathrooms & kitchens. Exceptions are for receptacle outlets for appliances that are generally not moved (my assumption would be dishwashers, refrigerators, etc.). I believe NFPA has a free online access to the code if you don't have one.
    In my area, Los Angeles County, all of my projects requiring the installation of new or replacing receptacles requires them to be TR.
    Wut's up Gunnar... how was your Christmas? (If you celebrate)


  4. #4
    Join Date
    Feb 2008
    Location
    Caledon, Ontario
    Posts
    4,982

    Default Re: Tamper resistent electrical outlets

    Those tamper proof outlets are a pain in the butt. Always difficult to plug something in.


  5. #5
    Join Date
    Mar 2007
    Location
    Fletcher, NC
    Posts
    28,042

    Default Re: Tamper resistent electrical outlets

    Tamper-resistant receptacles came in the NEC with the 2008 NEC.

    Jerry Peck
    Construction/Litigation/Code Consultant - Retired
    www.AskCodeMan.com

  6. #6
    Join Date
    Mar 2007
    Location
    Santa Rosa, CA
    Posts
    3,154

    Default Re: Tamper resistent electrical outlets

    Oops. I found it in the 2011 NEC. It isn't 210.52, it's 406.12 in the 2011, 2014 and 2017. Looks like the IRC started requiring them in 2009.

    Quote Originally Posted by Marc M View Post
    In my area, Los Angeles County, all of my projects requiring the installation of new or replacing receptacles requires them to be TR.
    Wut's up Gunnar... how was your Christmas? (If you celebrate)
    That would explain why Marc said L.A. requires it.

    Christmas was lovely, Marc. Thank you. I had a bit of a head cold, but not so bad that I didn't enjoy myself. And you?

    Department of Redundancy Department
    Supreme Emperor of Hyperbole
    http://www.FullCircleInspect.com/

  7. #7
    Join Date
    Sep 2008
    Location
    so so, California
    Posts
    1,867

    Default Re: Tamper resistent electrical outlets

    Quote Originally Posted by Gunnar Alquist View Post
    Oops. I found it in the 2011 NEC. It isn't 210.52, it's 406.12 in the 2011, 2014 and 2017. Looks like the IRC started requiring them in 2009.



    That would explain why Marc said L.A. requires it.

    Christmas was lovely, Marc. Thank you. I had a bit of a head cold, but not so bad that I didn't enjoy myself. And you?
    Fantastic, thanks. My wife and I cleaned out the garage.. It's crazy the stuff you find when you start moving stuff around. lol
    Actually, what "is" crazy is the number of times you re- buy some of the tools etc you thought were lost.


  8. #8
    Join Date
    Mar 2007
    Location
    Garland, TX
    Posts
    652

    Default Re: Tamper resistent electrical outlets

    Quote Originally Posted by Jerry Peck View Post
    Tamper-resistant receptacles came in the NEC with the 2008 NEC.
    correct for residential
    2002 pediatric patient care areas
    NEC_Article_517_Tamper_Resistant_Receptacles.pdf
    now almost any area where children could be

    Last edited by BARRY ADAIR; 12-31-2016 at 08:51 AM.
    badair http://www.adairinspection.com Garland, TX 75042
    Commercial-Residential-Construction-EIFS-Stucco-ACMV-Infrared Thermography
    life is the random lottery of events followed by numerous narrow escapes...accept the good

  9. #9
    Join Date
    Mar 2007
    Location
    Santa Rosa, CA
    Posts
    3,154

    Default Re: Tamper resistent electrical outlets

    Quote Originally Posted by Marc M View Post
    My wife and I cleaned out the garage.
    C'mon up and help me clean out mine!

    - - - Updated - - -

    Quote Originally Posted by Jerry Peck View Post
    Tamper-resistant receptacles came in the NEC with the 2008 NEC.
    I didn't find it in the 2008. Must have still been looking in the wrong place.

    In CA, that would put it in the 2010 California codes and enforced in 2011. (so confusing! )

    Department of Redundancy Department
    Supreme Emperor of Hyperbole
    http://www.FullCircleInspect.com/

Tags for this Thread

Bookmarks

Posting Permissions

  • You may not post new threads
  • You may not post replies
  • You may not post attachments
  • You may not edit your posts
  •