Welcome to the InspectionNews - Home Inspection forums.
You are currently viewing InspectionNews as a guest which gives you limited access to view most discussions but not pictures. There are over 6,300 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, have access to post topics, communicate privately with other members, respond to polls, upload content and access many other special features. Registration is fast and simple so please, join InspectionNews today!
If you have any problems with the registration process or your account login, please contact us.
Why join InspectionNews? Read the Testimonials
|
|

10-14-2007, 12:00 PM
|
|
Member
|
|
Join Date: Sep 2007
Location: San Antonio TX
Posts: 69
|
|
|
Attic issues
Could I get some comments?
Thanks
Last edited by Zibby Swieca : 10-14-2007 at 12:08 PM.
|
|

10-14-2007, 12:17 PM
|
|
Member
|
|
Join Date: Mar 2007
Location: Woodland Park, CO.
Posts: 168
|
|
|
Re: Attic issues
In the first picture: all the yellow wires on the rear wall, are they coming from some type of outlet???
|
|

10-14-2007, 12:52 PM
|
|
Member
|
|
Join Date: Sep 2007
Location: San Antonio TX
Posts: 69
|
|
|
Re: Attic issues
They are water supply pipes.
|
|

10-14-2007, 01:01 PM
|
|
Member
|
|
Join Date: Mar 2007
Location: Woodland Park, CO.
Posts: 168
|
|
|
Re: Attic issues
Oh ok...
|
|

10-14-2007, 02:45 PM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Spring Hill (Nashville), TN
Posts: 1,676
|
|
|
Re: Attic issues
Uhh, the yellow lines are CSST gas lines, they are coming off a manifold. The Red and Blue are PEX water lines.
What information are you looking for?
|
|

10-14-2007, 03:46 PM
|
 |
Member
|
|
Join Date: Aug 2007
Location: Memphis TN.
Posts: 1,496
|
|
|
Re: Attic issues
Zibby,
In Picture 1 it looks like bathroom vent does not go through the roof.
It may dead end or Vent through a Soffit Vent neither is allowed.
The Gas and water service lines I'll leave to someone else.
Picture 2 The purlin,wed member,brace under the rafter is misaligned you can see the pencil marks where it should have been.
__________________
It Might have Choked Artie But it ain't gone'a choke Stymie!
Billy J. Stephens HI Service
Memphis TN.
Last edited by Billy Stephens : 10-14-2007 at 03:53 PM.
Reason: Brace under rafter
|
|

10-14-2007, 04:55 PM
|
|
Member
|
|
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 7,034
|
|
|
Re: Attic issues
As Scott asked "What information are you looking for?"
The yellow CSST gas lines are not properly supported.
That white plastic duct is not allowed for any use, much less in the attic.
The ceiling joists (based on the direction of the insulation and the boards laying on the insulation) are running perpendicular to the rafters, indicating that rafters ties will be required (but none are shown in the photo).
The PVC vent at the gable end needs to be strapped and supported.
The second photo shows a rafter only partially bearing on a 2x laid flat-wise (I am guessing that this was done to get more bearing than just the top of that 2x the flat-wise one is on). Is this at a valley?
|
|

10-14-2007, 05:10 PM
|
 |
Member
|
|
Join Date: Aug 2007
Location: Memphis TN.
Posts: 1,496
|
|
|