Home and Commercial Inspection Education

If you have any problems with the registration process or your account login, please contact us.

Reply
 
LinkBack Thread Tools Search this Thread
  #1 (permalink)  
Old 10-04-2009, 07:54 AM
Michael Carson's Avatar
Michael Carson Michael Carson is online now
Member
 
Join Date: Sep 2009
Location: Wausau, WI.
Posts: 28
Smoke Detectors In New Condo Not Connected.
Inspected a condo yesterday that is 3-4 years old. Stopped by the sales office to let them know I was heading over to start. Realtor came in from another office, saw me and said that she was surprised that someone would get an inspection on new condos since everything is taken care of by the maintenance department.

On top of other fit and finish and leaking faucet stuff I found that none of the smoke detectors are electrically connected. They just mounted the detector on the junction box and did not hook any of them up.

Nice
Attached Images
File Type: jpg PA029626.jpg (27.3 KB, 109 views)
__________________
Michael Carson
Inspect It Right Home Inspections L.L.C.
www.inspectitrighthomeinspection.com
Reply With Quote
F.I.R.E. provides fireplace education, consulting services, fire investigation and litigation support across the United States.
  #2 (permalink)  
Old 10-04-2009, 11:41 AM
Rick Cantrell Rick Cantrell is offline
Member
 
Join Date: Mar 2007
Location: Columbus GA
Posts: 778
Re: Smoke Detectors In New Condo Not Connected.
Around here smoke detectors are also required to be interconnected with battery backup.
__________________
Rick Cantrell
Columbus GA
Reply With Quote
  #3 (permalink)  
Old 10-04-2009, 12:45 PM
Raymond Wand Raymond Wand is online now
Member
 
Join Date: Feb 2008
Location: Caledon, Ontario
Posts: 1,131
Re: Smoke Detectors In New Condo Not Connected.
Well so much for the maintenance crew. Hope the place doesn't catch fire and someone is killed. Makes you wonder what is amiss in the other units.

Good find!
__________________
The value of experience is not in seeing much, but in seeing wisely. - Sir William Osler 1905
Reply With Quote
  #4 (permalink)  
Old 10-05-2009, 01:54 AM
ben jacks ben jacks is offline
Member
 
Join Date: May 2009
Location: Seattle
Posts: 133
Re: Smoke Detectors In New Condo Not Connected.
Quote:
Originally Posted by Michael Carson View Post
Inspected a condo yesterday that is 3-4 years old. Stopped by the sales office to let them know I was heading over to start. Realtor came in from another office, saw me and said that she was surprised that someone would get an inspection on new condos since everything is taken care of by the maintenance department.

On top of other fit and finish and leaking faucet stuff I found that
Quote:
none of the smoke detectors are electrically connected.
They just mounted the detector on the junction box and did not hook any of them up.

Nice
On top of that, the smoke alarm has no battery back-up, let alone an interconnecting parallel alarm conductor. I know WI State has adopted the smoke alarm 120Vac battery backup NFPA 72 Ch.11 requirement (1996) so this may have been a double violation. I notice that an AC whip is the interconnecting means and may not provide easy repair accessibility. I myself, would write it up requiring a hookup, but as a CYA just in case I would mention the missing battery and interconnecting conductor. A different smoke alarm may be needed. rbj
Reply With Quote
  #5 (permalink)  
Old 10-05-2009, 05:05 PM
Michael Carson's Avatar
Michael Carson Michael Carson is online now
Member
 
Join Date: Sep 2009
Location: Wausau, WI.
Posts: 28
Re: Smoke Detectors In New Condo Not Connected.
Quote:
Originally Posted by ben jacks View Post
On top of that, the smoke alarm has no battery back-up, let alone an interconnecting parallel alarm conductor. I know WI State has adopted the smoke alarm 120Vac battery backup NFPA 72 Ch.11 requirement (1996) so this may have been a double violation. I notice that an AC whip is the interconnecting means and may not provide easy repair accessibility. I myself, would write it up requiring a hookup, but as a CYA just in case I would mention the missing battery and interconnecting conductor. A different smoke alarm may be needed. rbj

I did write it up as requiring hookup according to local ordinances with applicable municipal inspection. The reason the battery is not there is because I had to remove it to get to the screw and loosen it. I did that so I could slide the detector aside to show the wiring along with the alarm for the picture.
Thank you for the info, I forgot the actual Ch. 11 requirement section.
__________________
Michael Carson
Inspect It Right Home Inspections L.L.C.
www.inspectitrighthomeinspection.com
Reply With Quote
  #6 (permalink)  
Old 10-05-2009, 07:57 PM
John Kogel's Avatar
John Kogel John Kogel is online now
Member
 
Join Date: Feb 2009
Location: Southern Vancouver Island
Posts: 537
Re: Smoke Detectors In New Condo Not Connected.
You say the battery was installed so the unit would test ok, but not be hard wired???

Dang, now I'm wondering how many more are out there not wired just like that?????
Reply With Quote
  #7 (permalink)  
Old 10-05-2009, 10:13 PM
Jerry Peck's Avatar
Jerry Peck Jerry Peck is online now
Member
 
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 14,297
Re: Smoke Detectors In New Condo Not Connected.
Quote:
Originally Posted by John Kogel View Post
You say the battery was installed so the unit would test ok, but not be hard wired???

Dang, now I'm wondering how many more are out there not wired just like that?????
John,

If they are hard-wired in and interconnected as required, not being wired in and having a battery will not trigger the other smoke detectors - only that one will go off.

That should be enough to write the smoke detectors up, and have the installation checked and corrected, which would include the wiring.

If hard-wired and actually connected, but not interconnected, the same thing would happen - only that one smoke detector would go off.
__________________
Jerry Peck, Construction / Litigation Consultant
Construction Litigation Consultants, LLC ( www.ConstructionLitigationConsultants.com )
www.AskCodeMan.com
Reply With Quote
  #8 (permalink)  
Old 10-07-2009, 10:25 PM
John Kogel's Avatar
John Kogel John Kogel is online now
Member
 
Join Date: Feb 2009
Location: Southern Vancouver Island
Posts: 537
Re: Smoke Detectors In New Condo Not Connected.
Quote:
Originally Posted by Jerry Peck View Post
John,

If they are hard-wired in and interconnected as required, not being wired in and having a battery will not trigger the other smoke detectors - only that one will go off.
Thanks Jerry, that's ..........logical !!
Reply With Quote
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Dual supply for smoke detectors Bob Schlack Building Interior: Home Inspection and Commercial Inspection 10 08-21-2009 03:40 PM
Smoke Detectors on AFCI Bedroom Circuit Nick Ostrowski Electrical Systems: Home Inspection and Commercial Inspection 27 07-21-2009 11:45 AM
Proper test on Smoke Detectors daniel nantell General Chit Chat: Home Inspectors & Commercial Inspectors 4 05-08-2009 02:19 PM
How often should smoke detectors be replaced? Jerry Peck Electrical Systems: Home Inspection and Commercial Inspection 15 08-15-2007 07:00 PM
smoke detectors wayne soper Building Interior: Home Inspection and Commercial Inspection 4 04-12-2007 01:58 PM

Alabama | Alaska | Arizona | Atlanta | Aurora | Austin | Baltimore | Boston | California | Cambridge | Cape Coral | Chandler | Charlotte | Chicago | Cincinnati | Clarksville | Cleveland | Colorado | Columbus | Connecticut | Dallas | Delaware | Denver | Detroit | Durham | El Paso | Eugene | Florida | Fort Worth | Fresno | Georgia | Gilbert | Hawaii | Henderson | Houston | Huntsville | Idaho | Illinois | Indiana | Indianapolis | Irvine | Jacksonville | Joliet | Kansas City | Knoxville | Lancaster | Las Vegas | Los Angeles | Louisiana | Louisville | Maine | Maryland | Massachusetts | Memphis | Mesa | Miami | Michigan | Milwaukee | Minneapolis | Minnesota | Miramar | Mississippi | Missouri | Montana | Nashville | Nebraska | Nevada | New Hampshire | New Jersey | New Mexico | New York | North Carolina | North Dakota | Oakland | Ohio | Oklahoma | Omaha | Ontario | Orange | Oregon | Orlando | Pennsylvania | Philadelphia | Phoenix | Pittsburgh | Plano | Portland | Port StLucie | Raleigh | Rhode Island | Roseville | Sacramento | Salem | San Antonio | San Diego | San Francisco | San Jose | Scottsdale | Seattle | Sioux falls | South Carolina | South Dakota | St Louis | Tampa | Tennessee | Texas | Thornton | Toledo | Tucson | Tulsa | Utah | Vancouver | Vermont | Virginia | West Virginia | Wichita | Wisconsin | Wyoming | Cost To Repair

All times are GMT -7. The time now is 04:52 PM.


Design by Vjacheslav Trushkin.
Powered by vBulletin® Version 3.6.5
Copyright ©2000 - 2009, Jelsoft Enterprises Ltd.
Search Engine Optimization by vBSEO 3.0.0 RC8
vB.Sponsors
All Rights Reserved. Hann Tech Marketing Link / InspectionNews.com / InspectionNews.net - No part of InspectionNews.net may be reproduced in any way, or by any means, without the prior written permission of InspectionNews.net. Use of any index or listing Software for the purpose of constructing a mailing list, creating promotional materials or producing a printed or electronic catalog of any kind is expressly forbidden without the prior written permission of InspectionNews.net - All text, graphics and design on InspectionNews.net is copyright by Hann Tech Marketing Links.
Ad Management by RedTyger