Re: understairway fire blocking
On the concealed wall side, fireblocking should be installed at the angle of the stringer and aligned with the bottom of the stringer.
On the non-concealed side, nothing needs to be done ... fire would just jump around everything and anything anyway as it is all exposed.
|