    I recently inspected a MH feeder. The HO used type TC cable rated for direct burial. It is #4 4 wire copper with a bare equipment ground under the outer covering. The service is 100 amps. Is this a code compliant installation??

    Similar Threads:
    OREP Insurance
    "Get correct views of life, and learn to see the world in its true light. It will enable you to live pleasantly, to do good, and, when summoned away, to leave without regret. " Robert E. Lee

  2. #2
    Fred Warner's Avatar
    Fred Warner Guest

    Default Re: Another mobile home feeder

    Quote Originally Posted by Roland Miller View Post
    I recently inspected a MH feeder. The HO used type TC cable rated for direct burial. It is #4 4 wire copper with a bare equipment ground under the outer covering. The service is 100 amps. Is this a code compliant installation??
    550.33 ('05) requires 4 insulated conductors or a listed cord. Is the TC tray cable? or is it listed for mobile home assembly?


  3. #3
    Join Date
    Oct 2008
    Location
    Tulsa, OK
    Posts
    544

    Default Re: Another mobile home feeder

    Fred- this is TC cable listed for direct burial all the way from the pedistal to the MH service equipment.