Residential Lightning Protection System Grounding
Is/Are the lightning system grounding electrode(s) allowed to be used as the required building or structure grounding electrode system?
Similar Threads:
-
02-09-2009, 06:01 PM #2
Re: Residential Lightning Protection System Grounding
My answer is--only if you don't connect the lightning protection system ground rods(electrodes) to the down leads..
OK--The real answer is no--they are separated systems but must be bonded together..250.106 (2008 ed)