    Default ground and neutral on same screw in main panel

    Hi everyone, just needed some confirmation on this. On the main feed coming in to the main panel they have the ground and neutral on the same screw. I'm pretty new, but it didn't look right to me. thanks for all the input ahead of time. I really do appreciate you guys.

    Similar Threads:
    Member Benefits1

  2. #2
    Join Date
    Mar 2007
    Location
    Fletcher, NC
    Posts
    28,042

    Default Re: ground and neutral on same screw in main panel

    Quote Originally Posted by Kevin Rutledge View Post
    On the main feed coming in to the main panel they have the ground and neutral on the same screw.

    The neutral is not allowed in any terminal with any other conductor, not even another neutral.

    Jerry Peck
    Construction/Litigation/Code Consultant - Retired
    www.AskCodeMan.com