Thread: AFCI Exception
-
04-21-2009, 10:00 AM #1
AFCI Exception
I inspected a home that had new service equipment.
I noticed that there were no AFCI breakers in the panel. I questioned this and the electrician told me that an amendment was made to the electrical code that states - AFCI breakers are not required for a service upgrade??
Can anyone confirm and provide the language for this exception?
Thanx
Similar Threads:
-
04-21-2009, 10:41 AM #2
Re: AFCI Exception
There is no exception because there is no requirement.
Replacing the service has nothing to do with the circuits needing AFCI protection.
*Installing new circuits* would be different, were any "new" circuits installed? If so, *those* new circuits would require AFCI protection.
-
04-23-2009, 04:59 AM #3
Re: AFCI Exception
There does appear to be a violation of the requirement for the cables to be secured within 12" of the panel.