Results 1 to 8 of 8
Thread: GFCI directly above kitchen sink
-
06-11-2009, 09:58 AM #1
GFCI directly above kitchen sink
What is the minimum distance a GFCI receptacle can be located near a sink?
Similar Threads:
-
06-11-2009, 10:05 AM #2
Re: GFCI directly above kitchen sink
You posted a good photo of how close one CAN be added, I've even seen them directly behind the faucet, but I'm not sure that is really any "closer" than yours.
Receptacle outlets "are not required to be" located behind the sink. They are "allowed to be" located there.
However, you do not measure from that receptacle 4 feet to the next closest receptacle to see if the number and placement of the receptacles meets the requirements, you would still measure 2 feet (24") from the edge of the sink to the next closest receptacle on that side - which means whoever installed those receptacles may likely have spaced the other receptacles incorrectly.
THAT would be what I would look for ... are the OTHER receptacles placed where required?
On the plumbing side of it, that does not provide much of a water resistant seal along the back of the countertop at the wall.
-
06-11-2009, 10:07 AM #3
Re: GFCI directly above kitchen sink
TT: NEC neither requires nor prohibits a receptacle in the space behind the sink. As long as it is installed above the flood rim it should be allowed.
-
06-11-2009, 10:10 AM #4
Re: GFCI directly above kitchen sink
-
06-11-2009, 10:13 AM #5
-
06-11-2009, 10:19 AM #6
Re: GFCI directly above kitchen sink
No wonder I could not find a minimum distance requirement. Thanks for quick responses.
-
06-11-2009, 12:40 PM #7
Re: GFCI directly above kitchen sink
-
06-11-2009, 12:44 PM #8
Re: GFCI directly above kitchen sink
I've seen the deep end edging your way lately, but I think you may have slipped off it.
Bookmarks