Results 1 to 9 of 9
Thread: How dumb am I....
-
10-08-2009, 09:47 AM #1
How dumb am I....
Situation... Two #12 wires connected to one 40 amp breaker. I call it out on the report as two wires on a single over sized breaker recommend replacing with two 20 amp breakers by a licensed electrician.
Listing agent calls me this morning.... "#12 wire is for 20 amps, I looked it up this morning. 20 amp and 20 amp is 40 so the one breaker is good. duh! Can't you even do math? How dumb are you? I need you to take it off the report and resend the report the buyer so they will stop asking for the repair"
Yeaaa... that's going to happen. I didn't even bother explaining. URG
Similar Threads:
-
10-08-2009, 10:02 AM #2
Re: How dumb am I....
How dumb are you?
-
10-08-2009, 10:18 AM #3
-
10-08-2009, 11:35 AM #4
Re: How dumb am I....
and I thought the only math they knew was $$$Sales x %%%% = Commission. I think they are improving.
-
10-08-2009, 11:41 AM #5
Re: How dumb am I....
Sure they can use it! Tell them to get a hacksaw and cut it in 1/2!
-
10-08-2009, 11:44 AM #6
-
10-08-2009, 06:20 PM #7
Re: How dumb am I....
A conductor cannot be connected in paralell unless it is 1/0 or larger. See 2005 NEC 310.4.
-
10-08-2009, 06:37 PM #8
Re: How dumb am I....
-
10-08-2009, 06:57 PM #9