    Default What is wrong with this goose neck connection?

    OREP Insurance

  2. #2
    Stacey Van Houtan's Avatar
    Stacey Van Houtan Guest

    Default Re: What is wrong with this goose neck connection?

    Looks good from my house


  3. #3
    Roger Frazee's Avatar
    Roger Frazee Guest

    Default Re: What is wrong with this goose neck connection?

    POCO will take issue with the mast and weather head being below the anchor point of the messenger. In your picture you will have excessive abrasion of the conductors insulation against the messenger wire from wind sway. The mast needs to be raised above the anchor point and the messenger wrap continued closer to the wedge before connecting to service entrance conductors and making the drip loop.


  4. #4
    Stacey Van Houtan's Avatar
    Stacey Van Houtan Guest

    Default Re: What is wrong with this goose neck connection?

    This is from my local Utility

    Attached Files Attached Files