Thread: Wiring markings
-
06-27-2007, 06:41 AM #1
Wiring markings
Last edited by Jeff Eastman; 12-20-2007 at 09:04 AM.
-
06-29-2007, 12:25 PM #2
Re: Wiring markings
No.
Basically, grounding and grounded conductors not part of a multiconductor cable and smaller than 6 AWG are to have the proper insulation color and reidentification is not allowed. Under NEC 250.119 B the reidentification of the grounding conductor in a multiconductor cable is allowed only if "condition of maintenance and supervision insure that only qualified persons service the installation."
Conductors smaller than 6 AWG are available in the proper colors for use as grounding and grounded conductors, and reidentification for those purposes is not allowed.
- BOB