    Default Service Entrance

    Has anyone seen this type of material before? I am not sure if this is wrapped around a metal conduit or not.

    Thanks,

    Ryan

    Similar Threads:
    ***IMPORTANT*** You Need To Register To View Images ***IMPORTANT*** You Need To Register To View Images
    OREP Insurance

  2. #2
    Join Date
    Mar 2007
    Location
    Spring Hill (Nashville), TN
    Posts
    5,851

    Default Re: Service Entrance

    Quote Originally Posted by Ryan Stouffer View Post
    Has anyone seen this type of material before? I am not sure if this is wrapped around a metal conduit or not.

    Thanks,

    Ryan
    Well it says "pipewrap" on the it! So logic would make me think that it is wrapped around the conduit..

    Scott Patterson, ACI
    Spring Hill, TN
    www.traceinspections.com

  3. #3
    Ryan Stouffer's Avatar
    Ryan Stouffer Guest

    Default Re: Service Entrance

    Okay. Maybe I should be more specific. I am 99% sure that it is wrapped around the conduit but I have never seen this type of material wrapped around a conduit before. Does anyone have any useful information as to why they may have done this?

    Thanks,

    Ryan


  4. #4
    Join Date
    Mar 2007
    Location
    Plano, Texas
    Posts
    185

    Default Re: Service Entrance

    PASCO’s “All Weather” Pipe Protection Tape is a tough
    PVC plastic tape with special high tack adhesives formulated
    to resist corrosion. It is easy to apply by hand with no
    special tools or equipment. It provides positive protection
    against abrasion and corrosive action for steel pipe, fittings
    & electrical conduit systems.
    Uses:
    • Corrosion protection for metal piping systems above and
    below ground.
    • Corrosion protection for fittings and joints on mill coated
    pipe.
    • Corrosion protection of electrical conduit & fittings.
    Features:
    • Resists corrosive action by salt water, soil acids, alkalies
    and salts.
    • Prevents dielectric corrosion between buried steel pipe
    and soil minerals.
    • Resists the effects of outdoor weathering and sunlight
    exposure.
    • High abrasion resistance.
    • Highly conformable over a wide temperature range.
    • Excellent insulating properties.
    • Resists commonly encountered chemicals and chemical
    vapors.
    • Protects against fungus and bacteria.
    • Standard widths.


  5. #5
    Ryan Stouffer's Avatar
    Ryan Stouffer Guest

    Default Re: Service Entrance

    Thanks. I appreciate it.


  6. #6
    Join Date
    Mar 2009
    Location
    Colorado Front Range
    Posts
    684

    Default Re: Service Entrance

    The NEC has the following regarding direct burial of metal conduit.

    300.6 Protection Against Corrosion and Deterioration.
    Raceways, cable trays, cablebus, auxiliary gutters, cable
    armor, boxes, cable sheathing, cabinets, elbows, couplings,
    fittings, supports, and support hardware shall be of materials
    suitable for the environment in which they are to be
    installed.

    (3) In Concrete or in Direct Contact with the Earth.
    Ferrous metal raceways, cable armor, boxes, cable sheathing,
    cabinets, elbows, couplings, nipples, fittings, supports,
    and support hardware shall be permitted to be installed in
    concrete or in direct contact with the earth, or in areas
    subject to severe corrosive influences where made of material
    approved for the condition, or where provided with
    corrosion protection approved for the condition.

    Most soil has a corrosive effect on metallic conduit and wrapping is good practice in any case.

    PVC is generally a better option. I've dug up plenty of metallic conduit that consisted of a tube of asphalt/rubber filled with iron oxide