Electrical cables contacting each other
Last edited by Scott Lynch; 12-20-2007 at 04:26 PM.
-
07-20-2007, 12:52 PM #2
Re: Electrical cables contacting each other
What are the cables in question? Power and control wiring ?
-
07-20-2007, 03:07 PM #3
Re: Electrical cables contacting each other
That's called "bundling" and causes those to need to be derated. 4-6 conductors are to be derated to 80%, which would still be on a 15 amp breaker.
Not that I like it, but with just those two there, I would write it up, but not make a big deal about it. It will likely not affect the furnace, and the attic light will be nowhere near rated amperage for that circuit, so derating would not affect the attic light at all.