    Default Double Tapped - Stranded vs Solid

    Determining if a double tapped breaker terminal is accetable or not, depends only on wether or not the breaker is listed for 2 wires (i.e. SD & CH). Wether the conductor is stranded or solid does not matter (i.e. two stranded ok but two solids not...), correct?

    Similar Threads:
    Inspection Referral

  2. #2
    Join Date
    Mar 2007
    Location
    Ormond Beach, Florida
    Posts
    26,252

    Default Re: Double Tapped - Stranded vs Solid

    Quote Originally Posted by Andrew Kolar View Post
    Wether the conductor is stranded or solid does not matter (i.e. two stranded ok but two solids not...), correct?

    That is correct.

    Jerry Peck, Construction / Litigation Consultant
    Construction Litigation Consultants, LLC ( www.ConstructionLitigationConsultants.com )
    www.AskCodeMan.com