12-19-2012, 03:21 PM #1
No main electrical disconnect located outside!
I could not find an outside electrical main disconnect breaker today just a meter. I opened the inside panel box and this is what i found! Why would anybody do this?
Similar Threads:
-
12-19-2012, 03:37 PM #2
Re: No main electrical disconnect located outside!
your pic is very out of focus, but it looks like an FPE panel with a split buss. The top can have 6 throws and that serves as the disconnecting means. There doesn't have to be a main outside unless the locals have modified the codes.
"Get correct views of life, and learn to see the world in its true light. It will enable you to live pleasantly, to do good, and, when summoned away, to leave without regret. " Robert E. Lee
-
12-19-2012, 04:52 PM #3
Re: No main electrical disconnect located outside!
That was done in a factory. I agree that it looks typical of a split bus panel arrangement. A larger view of the panel would help.
All answers based on unamended National Electrical codes.
-