    Default No main electrical disconnect located outside!

    I could not find an outside electrical main disconnect breaker today just a meter. I opened the inside panel box and this is what i found! Why would anybody do this?

    Similar Threads:
    ***IMPORTANT*** You Need To Register To View Images ***IMPORTANT*** You Need To Register To View Images
    Crawl Space Creeper

  2. #2
    Join Date
    Oct 2008
    Location
    Tulsa, OK
    Posts
    544

    Default Re: No main electrical disconnect located outside!

    your pic is very out of focus, but it looks like an FPE panel with a split buss. The top can have 6 throws and that serves as the disconnecting means. There doesn't have to be a main outside unless the locals have modified the codes.

    "Get correct views of life, and learn to see the world in its true light. It will enable you to live pleasantly, to do good, and, when summoned away, to leave without regret. " Robert E. Lee

  3. #3
    Join Date
    Aug 2008
    Location
    Maryland
    Posts
    1,970

    Default Re: No main electrical disconnect located outside!

    That was done in a factory. I agree that it looks typical of a split bus panel arrangement. A larger view of the panel would help.

    All answers based on unamended National Electrical codes.

  4. #4
    Royce Moore's Avatar
    Royce Moore Guest

    Default Re: No main electrical disconnect located outside!

    Quote Originally Posted by Jim Port View Post
    That was done in a factory. I agree that it looks typical of a split bus panel arrangement. A larger view of the panel would help.
    Thanks for the info. I understand it now.