Thread: Panel meltdown mystery
-
04-21-2014, 08:02 AM #1
Panel meltdown mystery
Mystery of this panel meltdown, even the electrician did not know cause.
Both HVAC breakers blew out and melted.
Main 200 amp did not trip.
Not sure of brand, electrician removed only leaving buss.
A few days prior HVAC tech sold her on installing a surge protector, they claim blowout not connected to their work.
Lucky the home did not burn, she was home at the time.
-
04-21-2014, 08:21 AM #2
Re: Panel meltdown mystery
Little more than a guess:
One (maybe two) breakers were loose on the buss bar.
This caused overheating at the connection of the breaker and buss bar.
Buss bar overheated and melted.
The melted material contacted the opposite buss bar, creating a direct short.
The short was only protected by the 200 amp main.
Thus, the blowout you see.
Again, just speculation.
' correct a wise man and you gain a friend... correct a fool and he'll bloody your nose'.
-
04-21-2014, 05:51 PM #3
Re: Panel meltdown mystery
I have looked at a couple panels that have fried like that. I usually assume that it is loose connections, but once things burn up like that it is hard to say.
-
04-21-2014, 05:57 PM #4
-
04-22-2014, 08:03 AM #5
Re: Panel meltdown mystery
I find it amazing sometimes how many homeowners accept all kinds of explanations from contractors.
Unrelated, but this past weekend I was visiting my daughter who lives near Rockville, MD. A neighbor just had a contractor install a granite counter top. During the installation he broke it in half. His response was that he would pay for 1/2 of a new one. Apparently one guy was balancing the CT on his knee when this happened.
-
04-28-2014, 06:55 AM #6
Re: Panel meltdown mystery
Don Hester
NCW Home Inspections, LLC
Wa. St. Licensed H I #647, WSDA #80050, http://www.ncwhomeinspections.com
-
05-02-2014, 03:58 PM #7
Re: Panel meltdown mystery
Can't tell by the pic but if this was one of the back-fed main types, that would be my first guess.
Replaced a few 'guts' on that type which looked just this way.
I could answer the question with good pics but obviously the evidence has been a tampered wit!!
All the HVAC guys I know think they are qualified. Sheesh
-
05-04-2014, 11:37 AM #8
Re: Panel meltdown mystery
The panel interior is a Challenger, notice the stabs for the Zinsco main breaker above the damaged stabs. It's a cheap panel & what do you expect?
-
05-11-2014, 11:46 AM #9
Re: Panel meltdown mystery
Looks like either a Bryant or Murray brand. Murray is well known for this, especially the red body main breakers.
Most likely a poor connection/arcing at the stab that generated a lot of heat melting everything around it.