Results 1 to 21 of 21
-
11-03-2014, 05:27 PM #1
-
11-03-2014, 05:34 PM #2
Re: Light switch proximity to entry door
Unfortunately, the only code which addresses that is the code of common sense.
-
11-03-2014, 05:38 PM #3
Re: Light switch proximity to entry door
-
11-03-2014, 05:56 PM #4
Re: Light switch proximity to entry door
The requirement is for a switch controlled lighting outlet or receptacle in the room. The switch location is not mandated as it is a design issue. The switch could be located in the basement near the panel if one so chooses and it would meet the code.
All answers based on unamended National Electrical codes.
-
11-03-2014, 09:58 PM #5
Re: Light switch proximity to entry door
Last edited by Mark Hagenlock; 11-03-2014 at 10:03 PM.
-
11-04-2014, 07:07 AM #6
Re: Light switch proximity to entry door
In AZ.. The switch is required to be on the opposite side of the hinge.
Phoenix AZ Resale Home, Mobile Home, New Home Warranty Inspections. ASHI Certified Inspector #206929 Arizona Certified Inspector # 38440
www.inspectaz.com
-
11-04-2014, 10:06 AM #7
-
11-04-2014, 06:13 PM #8
Re: Light switch proximity to entry door
All boxes for switches should be located on the side of the door frame opposite the hinge.
Contractor should make necessary repairs.
This is a reply from a builder to a new home owner on a one year inspection last week..
The customers concern is , her 80 year old mother has to enter the room and turn the switch on that's on the back side of the door.
" There was also one item that we believe is not an issue. The report indicates a switch in the wall behind the hinge at the front bedroom. It is actually in a wall perpendicular to the door wall. The reason for this location was also due to the fact that we may not have the support necessary near the door since the modification indicates we framed for an additional door into that room. I included the mod sheet for reference. The challenge also is that there will be demolition and full repairs versus touch ups required to move the switch.
Last edited by Dan Harris; 11-04-2014 at 06:26 PM.
Phoenix AZ Resale Home, Mobile Home, New Home Warranty Inspections. ASHI Certified Inspector #206929 Arizona Certified Inspector # 38440
www.inspectaz.com
-
11-04-2014, 06:20 PM #9
Re: Light switch proximity to entry door
-
11-04-2014, 06:23 PM #10
-
11-04-2014, 06:28 PM #11
Re: Light switch proximity to entry door
Phoenix AZ Resale Home, Mobile Home, New Home Warranty Inspections. ASHI Certified Inspector #206929 Arizona Certified Inspector # 38440
www.inspectaz.com
-
11-04-2014, 06:31 PM #12
Re: Light switch proximity to entry door
I looked up Arizona building codes and found that building codes are adopted locally (that must really confuse contractors as there would be so many different variations of the codes) - anyway, Mesa, Arizona has adopted these codes (in addition to other codes, but these are for dwellings):
- IRC with the following amendments:
- - http://www.mesaaz.gov/clerk/codebook...F/T4/T4Ch3.pdf
- NEC with the following amendments:
- - http://mesaaz.gov/clerk/CodeBook/CodeinPDF/T4/T4Ch4.pdf
I may have missed it, but I did not see anything about the location of light switches in those codes.
-
11-04-2014, 06:42 PM #13
-
11-04-2014, 07:00 PM #14
Re: Light switch proximity to entry door
Phoenix AZ Resale Home, Mobile Home, New Home Warranty Inspections. ASHI Certified Inspector #206929 Arizona Certified Inspector # 38440
www.inspectaz.com
-
11-04-2014, 07:17 PM #15
Re: Light switch proximity to entry door
http://www.azroc.gov/Acrobat/Public/..._Standards.pdf
Bottom of pg 19 and top of page 20
Phoenix AZ Resale Home, Mobile Home, New Home Warranty Inspections. ASHI Certified Inspector #206929 Arizona Certified Inspector # 38440
www.inspectaz.com
-
11-04-2014, 08:40 PM #16
Re: Light switch proximity to entry door
How about starting at the top of Page 1?
(bold and underlining are mine)
INTRODUCTION
These standards cover performance of those construction items of major concern to the buyer for the first two years of ownership, unless otherwise specified. The contractor should stand behind the product, but the buyer should be responsible for owner-maintenance items. Contractor responsibility under these standards should not extend to items which have been subject to owner neglect, modification or abnormal use.
The effective date for the start of coverage of these standards should begin with the close of escrow, when the buyer occupies the structure, or the date of discovery, whichever occurs first or as otherwise noted.
Defects in appliances and plumbing and electrical fixtures properly installed by the contractor should be limited to the manufacturer's warranty.
These standards are subject to revision as methods of construction or materials used in construction continue to change. If there is any conflict between the workmanship standards and building code requirements, the latter should prevail.
RULE 4-9-108 WORKMANSHIP STANDARDS
A. A contractor shall perform all work in a professional and workmanlike manner.
B. A contractor shall perform all work in accordance with any applicable building codes and professional industry standards.
C. All work performed by a contractor in a county, city, or town that has not adopted building codes or where any adopted building codes do not contain specific provisions applicable to that aspect of construction work shall be performed in accordance with professional industry standards.
Then what follows for definitions reads more like something for a home inspection report guide than a "Workmanship Standard for Licensed Contractors" in that someone is expected to be writing these things up:
DEFINITIONS
The following standards are expressed in terms of permissible tolerances. The format is designed for easy comprehension as follows:
PD Possible deficiency
A brief statement of the problem to be considered.
AT Acceptable tolerance
A statement in measurable terms above which repair may be required and below which the condition is considered to be acceptable. “None” means that the possible deficiency identified is completely unacceptable and no tolerance is allowed.
CR Contractor responsibility
A statement of the corrective action needed to correct the deficiency or damage.
There are A LOT of things which "should" be done", and far fewer things which "shall" be done throughout life and business in order to live a "good life" and operate a "good business" with "good practices" for each ... but "shall" - if only that were true ...
-
11-04-2014, 09:52 PM #17
Re: Light switch proximity to entry door
Page 19 is about painting, page 20 is about plumbing. The correct pages numbers are 13 and 14.
From the Definitions page:
PD Possible deficiency
A brief statement of the problem to be considered.
AT Acceptable tolerance
A statement in measurable terms above which repair may be required
and below which the condition is considered to be acceptable. “None”
means that the possible deficiency identified is completely unacceptable
and no tolerance is allowed.
CR Contractor responsibility
A statement of the corrective action needed to correct the deficiency or
damage.
From page 13: PD Switch located behind door.
From page 14: AT All boxes for switches should be located on the side of the
doorframe opposite the hinge.
Using the loosely worded reference materials from the enforcement agency leaves a lot to interpretation and dispute.
Last edited by Jim Port; 11-05-2014 at 09:15 AM. Reason: corrected page numbers and added addtl.
All answers based on unamended National Electrical codes.
-
11-05-2014, 09:23 AM #18
Re: Light switch proximity to entry door
The rule contradicts itself. A switch behind a door is listed as a possible deficiency, not an absolute that the "all switches should be..." should mean.
Again, the picture as shown meets all the vague requirements as set forth be the AHJ.
Also the CR is a stand-alone notation and not a continuance about the possible deficiency.
All answers based on unamended National Electrical codes.
-
11-05-2014, 05:18 PM #19
Re: Light switch proximity to entry door
A fan light fixture, with remote control in a holder by the door Shall be an easy solution.
John Kogel, RHI, BC HI Lic #47455
www.allsafehome.ca
-
11-06-2014, 10:24 AM #20
Re: Light switch proximity to entry door
You are correct on the pg #s I was taking the #s off of the PDF file..
I found what ever it takes to get a defect corrected by the builder works best for me and the new home owners.
To date anything disputed by the builder, the ROC investigator found the defect should be corrected and in favor of the customer , end result the builder corrected the defect based on the "loosely worded" ROC standards.
Phoenix AZ Resale Home, Mobile Home, New Home Warranty Inspections. ASHI Certified Inspector #206929 Arizona Certified Inspector # 38440
www.inspectaz.com
-
11-06-2014, 10:48 AM #21
Re: Light switch proximity to entry door
Even the standard says this is a possible defect, not an absolute. Either the builders are unwilling to question an inspector or just afraid of losing a sale.
All answers based on unamended National Electrical codes.
Bookmarks