Thread: Equipment ground
-
11-18-2007, 07:10 AM #1
Equipment ground
Last edited by dan orourke; 12-26-2007 at 10:54 AM.
-
11-18-2007, 07:48 AM #2
Re: Equipment ground
Yes. And the neutrals should be separate from the equipment grounds and not bonded to the panel.
"There is no exception to the rule that every rule has an exception." -James Thurber, writer and cartoonist (1894-1961)
www.ArnoldHomeInspections.com
-
11-18-2007, 01:40 PM #3
Re: Equipment ground
To add to John's "Yes." ... not only is it 'allowed to be', it is also "required to be" bonded to those enclosures.