Wiring in A/C disconnect box
Last edited by Scott Lynch; 12-20-2007 at 04:45 PM.
-
12-10-2007, 05:13 PM #2
Re: Wiring in A/C disconnect box
Scott
The 14 gauge wire is not connected to this HVAC disconnect box and should be enclosed in it's own box.
Last edited by Billy Stephens; 12-10-2007 at 05:27 PM. Reason: HVAC
It Might have Choked Artie But it ain't gone'a choke Stymie! Our Gang " The Pooch " (1932)
Billy J. Stephens HI Service Memphis TN.
-
12-10-2007, 05:35 PM #3
Re: Wiring in A/C disconnect box
That's the low voltage wiring ... see it coming out of the fitting with the power conductors?
*NOT ALLOWED* in the same raceway or enclosure as the power conductors.
By the way, you also wrote up the white wire with the red tape, right?