Results 1 to 2 of 2

Thread: Panel Bonding

  1. #1
    Wendell Swedberg's Avatar
    Wendell Swedberg Guest

    Default Panel Bonding

    Last edited by Wendell Swedberg; 03-01-2008 at 08:22 PM.
    Inspection Referral

  2. #2
    Join Date
    Mar 2007
    Location
    Philadelphia PA
    Posts
    3,177

    Default Re: Panel Bonding

    The neutrals (grounded conductors) and equipment grounds are only allowed to be bonded to each other at the service equipment. Everywhere else they should be separated and the neutrals should be isolated from the enclosures and the equipment grounds should be bonded to the enclosures.


Bookmarks

Posting Permissions

  • You may not post new threads
  • You may not post replies
  • You may not post attachments
  • You may not edit your posts
  •