Results 1 to 5 of 5
Thread: Denergizing Panel Requirement
-
05-13-2008, 07:15 AM #1
Denergizing Panel Requirement
Does anybody have an idea how long it has been required for service panels to need no more than 6 throws of the hand to denergize the entire panel? I saw an older split bus panel yesterday that needed 10 throws to shut it down.
Similar Threads:
-
05-13-2008, 07:27 AM #2
Re: Denergizing Panel Requirement
I don't think there was ever a time 10 was okay. All I've ever heard was 6 and now 1. I suppose it's possible that there was a time period that it just wasn't addressed so you could find anything.
But really, circuit breakers didn't come about until the 50's/60's and by the 60's I'm pretty sure it was the 6 throws of the hand rule. I seem to remember even the old Pushmatic panels from the 50's/60's had a 'sub-main' and fell under the 6 switches.
-
05-13-2008, 09:14 AM #3
Re: Denergizing Panel Requirement
Back before time began ...
If there were more than 6 in the section which serves as the main (and which controls the other section), then it was improperly done, with improper breakers (the label will show a schematic showing the double pole breakers in the 'main' section, and it probably will not show any single pole breaker in that section - because that would allow the total number of 'mains' to exceed 6).
-
05-13-2008, 12:00 PM #4
Re: Denergizing Panel Requirement
6 disconnects is still the rule However these need to be grouped together and labeled. I have been in business since 1977 and there was never 10 disconnects allowed. Also becareful if it is a split bus panel as there are little different.
-
05-13-2008, 10:01 PM #5
Re: Denergizing Panel Requirement
Thanks guys.
Bookmarks