Results 1 to 5 of 5
  1. #1
    Join Date
    Mar 2007
    Location
    Spring City/Surrounding Philadelphia area
    Posts
    3,509

    Default Denergizing Panel Requirement

    Does anybody have an idea how long it has been required for service panels to need no more than 6 throws of the hand to denergize the entire panel? I saw an older split bus panel yesterday that needed 10 throws to shut it down.

    Similar Threads:
    OREP Insurance

  2. #2
    Join Date
    Mar 2007
    Location
    Oregon
    Posts
    2,365

    Default Re: Denergizing Panel Requirement

    I don't think there was ever a time 10 was okay. All I've ever heard was 6 and now 1. I suppose it's possible that there was a time period that it just wasn't addressed so you could find anything.

    But really, circuit breakers didn't come about until the 50's/60's and by the 60's I'm pretty sure it was the 6 throws of the hand rule. I seem to remember even the old Pushmatic panels from the 50's/60's had a 'sub-main' and fell under the 6 switches.


  3. #3
    Join Date
    Mar 2007
    Location
    Fletcher, NC
    Posts
    28,042

    Default Re: Denergizing Panel Requirement

    Quote Originally Posted by Nick Ostrowski View Post
    Does anybody have an idea how long it has been required for service panels to need no more than 6 throws of the hand to denergize the entire panel? I saw an older split bus panel yesterday that needed 10 throws to shut it down.
    Back before time began ...

    If there were more than 6 in the section which serves as the main (and which controls the other section), then it was improperly done, with improper breakers (the label will show a schematic showing the double pole breakers in the 'main' section, and it probably will not show any single pole breaker in that section - because that would allow the total number of 'mains' to exceed 6).

    Jerry Peck
    Construction/Litigation/Code Consultant - Retired
    www.AskCodeMan.com

  4. #4
    Richard Abrams's Avatar
    Richard Abrams Guest

    Cool Re: Denergizing Panel Requirement

    6 disconnects is still the rule However these need to be grouped together and labeled. I have been in business since 1977 and there was never 10 disconnects allowed. Also becareful if it is a split bus panel as there are little different.


  5. #5
    Join Date
    Mar 2007
    Location
    Spring City/Surrounding Philadelphia area
    Posts
    3,509

    Default Re: Denergizing Panel Requirement

    Thanks guys.


Bookmarks

Posting Permissions

  • You may not post new threads
  • You may not post replies
  • You may not post attachments
  • You may not edit your posts
  •