Results 1 to 3 of 3
  1. #1
    Ted Menelly's Avatar
    Ted Menelly Guest

    Default Grounding rod directly below Hose bib

    I just had a call from a man asking me about a grounding rod below a hose bib.

    I told him no problem.

    Hmmm, is there a problem with that?

    Ted

    Similar Threads:
    OREP Insurance

  2. #2
    Join Date
    Mar 2007
    Location
    Fletcher, NC
    Posts
    28,042

    Default Re: Grounding rod directly below Hose bib

    Not as long as they don't whack the hose bibb off with the sledge hammer driving the ground rod in.

    Actually, with the hose bibb being above it, that area may stay wetter than it otherwise would, thereby making it more useful because the resistance between the rod and earth would be less.

    Heck, leave the hose bibb on 'drip'.

    Jerry Peck
    Construction/Litigation/Code Consultant - Retired
    www.AskCodeMan.com

  3. #3
    Ted Menelly's Avatar
    Ted Menelly Guest

    Default Re: Grounding rod directly below Hose bib

    Thanks Jerry

    I new there was some crazy thought rolling around in this empty space of a brain of mine on "is there a problem".

    Ted


Bookmarks

Posting Permissions

  • You may not post new threads
  • You may not post replies
  • You may not post attachments
  • You may not edit your posts
  •