    I just had a call from a man asking me about a grounding rod below a hose bib.

    I told him no problem.

    Hmmm, is there a problem with that?

    Ted

    Similar Threads:
    Elite MGA Home Inspector E&O Insurance

  2. #2
    Join Date
    Mar 2007
    Location
    Ormond Beach, Florida
    Posts
    25,304

    Default Re: Grounding rod directly below Hose bib

    Not as long as they don't whack the hose bibb off with the sledge hammer driving the ground rod in.

    Actually, with the hose bibb being above it, that area may stay wetter than it otherwise would, thereby making it more useful because the resistance between the rod and earth would be less.

    Heck, leave the hose bibb on 'drip'.

    Jerry Peck, Construction / Litigation Consultant
    Construction Litigation Consultants, LLC ( www.ConstructionLitigationConsultants.com )
    www.AskCodeMan.com

  3. #3
    Join Date
    Mar 2007
    Location
    Fort Worth, Texas
    Posts
    5,392

    Default Re: Grounding rod directly below Hose bib

    Thanks Jerry

    I new there was some crazy thought rolling around in this empty space of a brain of mine on "is there a problem".

    Ted