InspectionNews - Home Inspection



Registration is FREE!... and will get rid of this top message

Welcome to InspectionNews.net.

You are currently viewing InspectionNews as a guest which gives you limited access to view some discussions but none of the pictures.

There are over 9,970 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, post new topics or reply to others, communicate privately with other members, respond to polls, upload content and access many other special features.

Registration is FREE for you because the sponsors pay your way. Please visit the sponsors often and let them know that you found them on InspectionNews!

Registration is FREE, fast and easy so please, join InspectionNews today!

Why join InspectionNews? Read the Testimonials

Looking for Education? We recommend Casey, O'Malley and Associates
Home and Commercial Inspection Education

If you have any problems with the registration process or your account login, please contact us.

Reply
 
LinkBack Thread Tools Search this Thread
  #1 (permalink)  
Old 07-08-2009, 09:09 PM
mathew stouffer mathew stouffer is online now
Member
 
Join Date: Mar 2008
Location: Park City, Utah
Posts: 649
Floor outlets
Do floor outlets require covers?
Attached Images
File Type: jpg SDC12605.jpg (54.1 KB, 144 views)
Reply With Quote
HomeGauge Reports
  #2 (permalink)  
Old 07-08-2009, 09:15 PM
Gunnar Alquist's Avatar
Gunnar Alquist Gunnar Alquist is offline
Member
 
Join Date: Mar 2007
Location: Santa Rosa, CA
Posts: 1,198
Re: Floor outlets
Quote:
Originally Posted by mathew stouffer View Post
Do floor outlets require covers?
Matthew,

Yes. They need to be specifically designed for floors. The outlet should be recessed below the surface of the floor and the plate should be strong enough to bear weight. I believe the box needs to be strong enough to bear weight as well.
Attached Images
File Type: jpg 5_outletbox_img_20076310272.jpg (53.1 KB, 41 views)
File Type: jpg 800px-Electrical_outlet_in_floor.jpg (98.2 KB, 60 views)
__________________
We have enough youth, how about a fountain of Smart?
Reply With Quote
  #3 (permalink)  
Old 07-08-2009, 09:18 PM
mathew stouffer mathew stouffer is online now
Member
 
Join Date: Mar 2008
Location: Park City, Utah
Posts: 649
Re: Floor outlets
Thanks Gunnar.
Reply With Quote
  #4 (permalink)  
Old 07-08-2009, 11:38 PM
Rollie Meyers Rollie Meyers is online now
Member
 
Join Date: Dec 2007
Location: Chico,Ca
Posts: 82
Re: Floor outlets
Here is a copy & paste from the 2008 NEC which is unchanged from the 2002 & 2005 editions.
314.27

(C) Floor Boxes. Boxes listed specifically for this application
shall be used for receptacles located in the floor.

Exception: Where the authority having jurisdiction judges
them free from likely exposure to physical damage, moisture,
and dirt, boxes located in elevated floors of show
windows and similar locations shall be permitted to be
other than those listed for floor applications. Receptacles
and covers shall be listed as an assembly for this type of
location.

This is my opinion, but that receptacle in the picture does not meet that exception.
Reply With Quote
  #5 (permalink)  
Old 07-09-2009, 07:45 AM
mathew stouffer mathew stouffer is online now
Member
 
Join Date: Mar 2008
Location: Park City, Utah
Posts: 649
Re: Floor outlets
Thanks. Once I looked at the distrution panel I figured these had to be wrong It was a mess.
Reply With Quote
  #6 (permalink)  
Old 07-09-2009, 09:28 AM
Jerry Peck's Avatar
Jerry Peck Jerry Peck is online now
Member
 
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 14,282
Re: Floor outlets
Quote:
Originally Posted by Rollie Meyers View Post
Here is a copy & paste from the 2008 NEC which is unchanged from the 2002 & 2005 editions.
314.27

(C) Floor Boxes. Boxes listed specifically for this application
shall be used for receptacles located in the floor.

Exception: Where the authority having jurisdiction judges
them free from likely exposure to physical damage, moisture,
and dirt, boxes located in elevated floors of show
windows and similar locations shall be permitted to be
other than those listed for floor applications. Receptacles
and covers shall be listed as an assembly for this type of
location.

This is my opinion, but that receptacle in the picture does not meet that exception.
Rollie,

"This is my opinion, but that receptacle in the picture does not meet that exception."

Not just "your opinion, that is what the code states,

That certainly does not look like it is "located in elevated floors of show
windows and similar locations". "Similar locations" would be floor areas which are not used for walking on, but for display - which is what show windows are not for (not for walking on) and are for (displaying items).

Additionally, when that exception is applied, the code states (bold and underlining are mine) "Receptacles and covers shall be listed as an assembly for this type of location".

Thus it is safe to say that is not allowed as shown in the photo.
__________________
Jerry Peck, Construction / Litigation Consultant
Construction Litigation Consultants, LLC ( www.ConstructionLitigationConsultants.com )
www.AskCodeMan.com
Reply With Quote
  #7 (permalink)  
Old 07-09-2009, 12:00 PM
Jerry McCarthy's Avatar
Jerry McCarthy Jerry McCarthy is offline
Member
 
Join Date: Mar 2007
Location: San Mateo, CA
Posts: 1,447
Re: Floor outlets
Let your mind picture a stout 200 + pound lady wearing stiletto heels coming down on that plastic receptacle outlet. I know........ Neither a pretty sight nor result.
__________________
Jerry McCarthy
Construction Consultant
www.expertbuildingconsultants.com
Reply With Quote
  #8 (permalink)  
Old 07-09-2009, 12:08 PM
Jerry Peck's Avatar
Jerry Peck Jerry Peck is online now
Member
 
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 14,282
Re: Floor outlets
Also, is it my imagination or an optical illusion ... that looks like it is in the middle of the top landing of a stairway, right where WC Jerry's referenced person will step on it.

Even a 110 lady in spike heels will poke that thing out, heck, even a man in large flat heels like are on men's shoes will crush that thing.

Not only that, but if on the landing as it looks, it is now a trip, slip and fall hazard as the surface is no longer level.
__________________
Jerry Peck, Construction / Litigation Consultant
Construction Litigation Consultants, LLC ( www.ConstructionLitigationConsultants.com )
www.AskCodeMan.com
Reply With Quote
  #9 (permalink)  
Old 07-20-2009, 05:18 AM
danyackoyd danyackoyd is offline
Member
 
Join Date: Jul 2009
Location: london
Posts: 1
Re: Floor outlets
I don't know about you guys but this picture just doesn't seems to be save. I know that it always happens that the electric components you want to use, are the furthest away for the closes socket, but putting a raised socket into the floor boarding doesn't seem to be the alternative for me. I don't know if by covering the socket any issue would be resolved.
Reply With Quote
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
GFCI outlets mathew stouffer Electrical Systems: Home Inspection and Commercial Inspection 3 07-25-2008 06:13 PM
outlets next to sink Jeff Eastman Electrical Systems: Home Inspection and Commercial Inspection 3 10-05-2007 04:40 PM
difficult outlets Matt Fellman Electrical Systems: Home Inspection and Commercial Inspection 4 09-27-2007 01:25 PM
Outlets under soffits John Stephenson Electrical Systems: Home Inspection and Commercial Inspection 3 06-02-2007 04:08 PM
CPSC Recall: Floor Electrical Outlets Brian Hannigan Electrical Systems: Home Inspection and Commercial Inspection 0 04-18-2007 12:29 PM

Alabama | Alaska | Arizona | Atlanta | Aurora | Austin | Baltimore | Boston | California | Cambridge | Cape Coral | Chandler | Charlotte | Chicago | Cincinnati | Clarksville | Cleveland | Colorado | Columbus | Connecticut | Dallas | Delaware | Denver | Detroit | Durham | El Paso | Eugene | Florida | Fort Worth | Fresno | Georgia | Gilbert | Hawaii | Henderson | Houston | Huntsville | Idaho | Illinois | Indiana | Indianapolis | Irvine | Jacksonville | Joliet | Kansas City | Knoxville | Lancaster | Las Vegas | Los Angeles | Louisiana | Louisville | Maine | Maryland | Massachusetts | Memphis | Mesa | Miami | Michigan | Milwaukee | Minneapolis | Minnesota | Miramar | Mississippi | Missouri | Montana | Nashville | Nebraska | Nevada | New Hampshire | New Jersey | New Mexico | New York | North Carolina | North Dakota | Oakland | Ohio | Oklahoma | Omaha | Ontario | Orange | Oregon | Orlando | Pennsylvania | Philadelphia | Phoenix | Pittsburgh | Plano | Portland | Port StLucie | Raleigh | Rhode Island | Roseville | Sacramento | Salem | San Antonio | San Diego | San Francisco | San Jose | Scottsdale | Seattle | Sioux falls | South Carolina | South Dakota | St Louis | Tampa | Tennessee | Texas | Thornton | Toledo | Tucson | Tulsa | Utah | Vancouver | Vermont | Virginia | West Virginia | Wichita | Wisconsin | Wyoming | Cost To Repair

All times are GMT -7. The time now is 05:15 PM.


Design by Vjacheslav Trushkin.
Powered by vBulletin® Version 3.6.5
Copyright ©2000 - 2009, Jelsoft Enterprises Ltd.
Search Engine Optimization by vBSEO 3.0.0 RC8
vB.Sponsors
All Rights Reserved. Hann Tech Marketing Link / InspectionNews.com / InspectionNews.net - No part of InspectionNews.net may be reproduced in any way, or by any means, without the prior written permission of InspectionNews.net. Use of any index or listing Software for the purpose of constructing a mailing list, creating promotional materials or producing a printed or electronic catalog of any kind is expressly forbidden without the prior written permission of InspectionNews.net - All text, graphics and design on InspectionNews.net is copyright by Hann Tech Marketing Links.
Ad Management by RedTyger