Welcome to InspectionNews.
Registration is FREE!
Why join InspectionNews? Read the Testimonials
You are currently viewing InspectionNews as a guest which gives you limited access to view some discussions but you will not see any of the pictures or technical bulletins that have been uploaded.
There are over 11,850 inspectors who have already joined InspectionNews, contributing over 100,700 posts. By joining InspectionNews you will be able to see the pictures, start new threads, reply to posts, communicate privately with other members, respond to polls, upload content and access many other special features.
If you are an inspector or thinking about becoming one, InspectionNews is the place for you.
Registration is FREE because the sponsors pay your way.
Please visit all the sponsors often and let them know that you found them on InspectionNews!
How much should an inspection cost? Click the banner below to find out.

If you have any problems with the registration process or your account login, please contact us.
Registration is easy, so please Join InspectionNews Today!
|
 |
 |
|
 |
|

07-08-2009, 09:09 PM
|
|
Member
|
|
Join Date: Mar 2008
Location: Park City, Utah
Posts: 761
|
|
|
Floor outlets
Do floor outlets require covers?
|
|

07-08-2009, 09:15 PM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Santa Rosa, CA
Posts: 1,322
|
|
|
Re: Floor outlets
Originally Posted by mathew stouffer
Do floor outlets require covers?
Matthew,
Yes. They need to be specifically designed for floors. The outlet should be recessed below the surface of the floor and the plate should be strong enough to bear weight. I believe the box needs to be strong enough to bear weight as well.
__________________
Reality is a crutch for people who can't handle drugs.
|
|

07-08-2009, 09:18 PM
|
|
Member
|
|
Join Date: Mar 2008
Location: Park City, Utah
Posts: 761
|
|
|
Re: Floor outlets
Thanks Gunnar.
|
|

07-08-2009, 11:38 PM
|
|
Member
|
|
Join Date: Dec 2007
Location: Chico,Ca
Posts: 101
|
|
|
Re: Floor outlets
Here is a copy & paste from the 2008 NEC which is unchanged from the 2002 & 2005 editions.
314.27
(C) Floor Boxes. Boxes listed specifically for this application
shall be used for receptacles located in the floor.
Exception: Where the authority having jurisdiction judges
them free from likely exposure to physical damage, moisture,
and dirt, boxes located in elevated floors of show
windows and similar locations shall be permitted to be
other than those listed for floor applications. Receptacles
and covers shall be listed as an assembly for this type of
location.
This is my opinion, but that receptacle in the picture does not meet that exception.
|
|

07-09-2009, 07:45 AM
|
|
Member
|
|
Join Date: Mar 2008
Location: Park City, Utah
Posts: 761
|
|
|
Re: Floor outlets
Thanks. Once I looked at the distrution panel I figured these had to be wrong  It was a mess.
|
|

07-09-2009, 09:28 AM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 14,976
|
|
|
Re: Floor outlets
Originally Posted by Rollie Meyers
Here is a copy & paste from the 2008 NEC which is unchanged from the 2002 & 2005 editions.
314.27
(C) Floor Boxes. Boxes listed specifically for this application
shall be used for receptacles located in the floor.
Exception: Where the authority having jurisdiction judges
them free from likely exposure to physical damage, moisture,
and dirt, boxes located in elevated floors of show
windows and similar locations shall be permitted to be
other than those listed for floor applications. Receptacles
and covers shall be listed as an assembly for this type of
location.
This is my opinion, but that receptacle in the picture does not meet that exception.
Rollie,
"This is my opinion, but that receptacle in the picture does not meet that exception."
Not just "your opinion, that is what the code states,
That certainly does not look like it is "located in elevated floors of show
windows and similar locations". "Similar locations" would be floor areas which are not used for walking on, but for display - which is what show windows are not for (not for walking on) and are for (displaying items).
Additionally, when that exception is applied, the code states (bold and underlining are mine) "Receptacles and covers shall be listed as an assembly for this type of location".
Thus it is safe to say that is not allowed as shown in the photo. 
|
|

07-09-2009, 12:00 PM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Healdsburg, CA
Posts: 1,464
|
|
|
Re: Floor outlets
Let your mind picture a stout 200 + pound lady wearing stiletto heels coming down on that plastic receptacle outlet. I know........ Neither a pretty sight nor result.
|
|

07-09-2009, 12:08 PM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 14,976
|
|
|
Re: Floor outlets
Also, is it my imagination or an optical illusion ... that looks like it is in the middle of the top landing of a stairway, right where WC Jerry's referenced person will step on it.
Even a 110 lady in spike heels will poke that thing out, heck, even a man in large flat heels like are on men's shoes will crush that thing.
Not only that, but if on the landing as it looks, it is now a trip, slip and fall hazard as the surface is no longer level.
|
|

07-20-2009, 05:18 AM
|
|
Member
|
|
Join Date: Jul 2009
Location: london
Posts: 1
|
|
|
Re: Floor outlets
I don't know about you guys but this picture just doesn't seems to be save. I know that it always happens that the electric components you want to use, are the furthest away for the closes socket, but putting a raised socket into the floor boarding doesn't seem to be the alternative for me. I don't know if by covering the socket any issue would be resolved.
|
|
| Thread Tools |
Search this Thread |
|
|
|
Posting Rules
|
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts
HTML code is Off
|
|
|
| Thread |
Thread Starter |
Forum |
Replies |
Last Post |
| GFCI outlets |
mathew stouffer |
Electrical Systems: Home Inspection and Commercial Inspection |
3 |
07-25-2008 06:13 PM |
| outlets next to sink |
Jeff Eastman |
Electrical Systems: Home Inspection and Commercial Inspection |
3 |
10-05-2007 04:40 PM |
| difficult outlets |
Matt Fellman |
Electrical Systems: Home Inspection and Commercial Inspection |
4 |
09-27-2007 01:25 PM |
| Outlets under soffits |