InspectionNews - Home Inspection



Registration is FREE!... and will get rid of this top message

Welcome to InspectionNews.net.

You are currently viewing InspectionNews as a guest which gives you limited access to view some discussions but none of the pictures.

There are over 9,970 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, post new topics or reply to others, communicate privately with other members, respond to polls, upload content and access many other special features.

Registration is FREE for you because the sponsors pay your way. Please visit the sponsors often and let them know that you found them on InspectionNews!

Registration is FREE, fast and easy so please, join InspectionNews today!

Why join InspectionNews? Read the Testimonials

Looking for Education? We recommend Casey, O'Malley and Associates
Home and Commercial Inspection Education

If you have any problems with the registration process or your account login, please contact us.

Reply
 
LinkBack Thread Tools Search this Thread
  #1 (permalink)  
Old 11-02-2009, 05:32 AM
Alan Harris Alan Harris is offline
Member
 
Join Date: May 2009
Location: louisiana
Posts: 2
appliance garage outlet
The permit inspector for a kitchen renovation I'm involved did not approve the 110 V duplex outlet inside the appliance garage. He claims that the outlet must be visible with the appliance garage door closed. Is this really a code requirement?
Reply With Quote
Are inspection referrals from past clients important to you? If so, click here to get even more referrals!
  #2 (permalink)  
Old 11-02-2009, 05:42 AM
Rick Cantrell Rick Cantrell is offline
Member
 
Join Date: Mar 2007
Location: Columbus GA
Posts: 777
Re: appliance garage outlet
Just speculating.
The IRC requires 2 outlets (on separate circuits) for kitchen counter-tops. That is in addition to any outlets that are for dedicated use. The inspector may consider that outlet to be dedicated use.
__________________
Rick Cantrell
Columbus GA
Reply With Quote
  #3 (permalink)  
Old 11-02-2009, 05:46 AM
Vern Heiler's Avatar
Vern Heiler Vern Heiler is online now
Member
 
Join Date: Mar 2008
Location: Charlotte NC
Posts: 628
Re: appliance garage outlet
Does the refrigerator or microwave outlet have to visible?
Reply With Quote
  #4 (permalink)  
Old 11-02-2009, 05:46 AM
Rick Cantrell Rick Cantrell is offline
Member
 
Join Date: Mar 2007
Location: Columbus GA
Posts: 777
Re: appliance garage outlet
Also there must be an outlet within 2' of all points on the counter-top. If the outlet is concealed the inspector might not count it as meeting this requirement.
__________________
Rick Cantrell
Columbus GA
Reply With Quote
  #5 (permalink)  
Old 11-02-2009, 05:51 AM
Rick Cantrell Rick Cantrell is offline
Member
 
Join Date: Mar 2007
Location: Columbus GA
Posts: 777
Re: appliance garage outlet
"Does the refrigerator or microwave outlet have to visible?"

Well, yes and no.
The outlets must be assessable for the appliance, but the outlets can be hidden behind the appliance, when the appliance is in place.
__________________
Rick Cantrell
Columbus GA
Reply With Quote
  #6 (permalink)  
Old 11-02-2009, 05:54 AM
Vern Heiler's Avatar
Vern Heiler Vern Heiler is online now
Member
 
Join Date: Mar 2008
Location: Charlotte NC
Posts: 628
Re: appliance garage outlet
Quote:
Originally Posted by Rick Cantrell View Post
"Does the refrigerator or microwave outlet have to visible?"

Well, yes and no.
The outlets must be assessable for the appliance, but the outlets can be hidden behind the appliance, when the appliance is in place.
Most of the microwave outlets I see are inside the wall cabinet above the microwave.
Reply With Quote
  #7 (permalink)  
Old 11-02-2009, 06:23 AM
Richard Pultar Richard Pultar is online now
Member
 
Join Date: Oct 2008
Location: new jersey
Posts: 181
Re: appliance garage outlet
ask the permit inspector ? for the code section ,
or ask his boss to tell him to give it to him so he can give it to you.
Or just do what the nut wants and move on .
Reply With Quote
  #8 (permalink)  
Old 11-02-2009, 06:36 AM
fritzkelly fritzkelly is online now
Member
 
Join Date: Mar 2007
Location: Camp Verde, Arizona
Posts: 794
Re: appliance garage outlet
Take the door off and replace when he leaves.
__________________
"Some people are like slinkies. They serve absolutely no useful purpose. But still put a smile on your face when pushed down a flight of stairs."
Reply With Quote
  #9 (permalink)  
Old 11-02-2009, 06:39 AM
Rollie Meyers Rollie Meyers is offline
Member
 
Join Date: Dec 2007
Location: Chico,Ca
Posts: 82
Re: appliance garage outlet
The appliance garage receptacle(s) do not count for the required countertop receptacles, but if they were trying to make it be part of them, is where I see a problem.
Reply With Quote
  #10 (permalink)  
Old 11-02-2009, 07:14 AM
Ray Norton Ray Norton is offline
Member
 
Join Date: May 2009
Location: Wisconsin
Posts: 17
Re: appliance garage outlet
NEC 210.52(C)(5) clarifies that a receptacle outlet in an appliance garage is not considered as one of the required countertop receptacle outlets.
Reply With Quote
  #11 (permalink)  
Old 11-02-2009, 07:55 AM
John Steinke's Avatar
John Steinke John Steinke is offline
Member
 
Join Date: Mar 2007
Location: Reno, Nv. - Now St. Louis, Mo.
Posts: 269
Re: appliance garage outlet
Canadian rules differ from US rules on this point. My answer is based upon the NEC, or "American Rules."

You can have receptacles inside an apppliance garage, but they do not count towards meeting the requirement for receptacles serving the countertop. Depending on the specific arrangement, this could very well mean that you would also need a receptacle right next to, or directly over, such a garage.
Reply With Quote
  #12 (permalink)  
Old 11-02-2009, 05:06 PM
ken horak ken horak is offline
Member
 
Join Date: Feb 2009
Location: usa
Posts: 275
Re: appliance garage outlet
Confront the inspector as a professional and request the code article he is using to make his/her ruling.

The appliance garage is treated just like a cabinet. It does not count toward the required counter top outlet. It does not need to be visable with the door closed. Does the microwave outlet in an upper cabinet need to be visable with the cabinet door closed? What about the disposal / dishwasher receptacle under the sink ?
Reply With Quote
  #13 (permalink)  
Old 11-02-2009, 06:03 PM
Jerry Peck's Avatar
Jerry Peck Jerry Peck is online now
Member
 
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 14,293
Re: appliance garage outlet
Quote:
Originally Posted by Alan Harris View Post
The permit inspector for a kitchen renovation I'm involved did not approve the 110 V duplex outlet inside the appliance garage. He claims that the outlet must be visible with the appliance garage door closed. Is this really a code requirement?
Quote:
Originally Posted by Rollie Meyers View Post
The appliance garage receptacle(s) do not count for the required countertop receptacles, but if they were trying to make it be part of them, is where I see a problem.
Quote:
Originally Posted by ken horak View Post
Confront the inspector as a professional and request the code article he is using to make his/her ruling.

The appliance garage is treated just like a cabinet. It does not count toward the required counter top outlet. It does not need to be visable with the door closed. Does the microwave outlet in an upper cabinet need to be visable with the cabinet door closed? What about the disposal / dishwasher receptacle under the sink ?
I think that when the inspector re-reads the code he will see where that is not required to be exposed ... as long as what Rollie referred to is not what he is applying - that you have ANOTHER receptacle to count for that wall space ... if you do not have ANOTHER receptacle to count for that wall space, then the inspector is correct.

Do this: measure from the appliance garage side to the nearest OTHER receptacle to the right - is that other receptacle within 24" horizontally along the wall line of the cabinet? If so, you would be okay to the right, so measure to the left, and if so again, you would be okay to the left too.

If you do not have ANOTHER receptacle within 24" to the right AND to the left, then you do have a problem.
__________________
Jerry Peck, Construction / Litigation Consultant
Construction Litigation Consultants, LLC ( www.ConstructionLitigationConsultants.com )
www.AskCodeMan.com
Reply With Quote
IC Home Inspection Report Writing
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
combustion appliance or plumbing? Bob Harper Plumbing System: Home Inspection and Commercial Inspection 5 08-06-2009 04:09 PM
Gas appliance question MaMa Mount Fireplaces, Chimneys and Solid Fuel Burning Appliances: Home Inspection and Commercial Inspection 3 05-06-2009 05:12 AM
Appliance venting Richard Roshak Fireplaces, Chimneys and Solid Fuel Burning Appliances: Home Inspection and Commercial Inspection 8 05-05-2008 07:24 PM
return air proximity to gas appliance? Jim McClendon Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection 2 04-23-2008 04:29 PM
Appliance Efficiency Site Michael Thomas Built-In Appliances and Systems: Home Inspection and Commercial Inspection 0 09-12-2007 03:37 PM

Alabama | Alaska | Arizona | Atlanta | Aurora | Austin | Baltimore | Boston | California | Cambridge | Cape Coral | Chandler | Charlotte | Chicago | Cincinnati | Clarksville | Cleveland | Colorado | Columbus | Connecticut | Dallas | Delaware | Denver | Detroit | Durham | El Paso | Eugene | Florida | Fort Worth | Fresno | Georgia | Gilbert | Hawaii | Henderson | Houston | Huntsville | Idaho | Illinois | Indiana | Indianapolis | Irvine | Jacksonville | Joliet | Kansas City | Knoxville | Lancaster | Las Vegas | Los Angeles | Louisiana | Louisville | Maine | Maryland | Massachusetts | Memphis | Mesa | Miami | Michigan | Milwaukee | Minneapolis | Minnesota | Miramar | Mississippi | Missouri | Montana | Nashville | Nebraska | Nevada | New Hampshire | New Jersey | New Mexico | New York | North Carolina | North Dakota | Oakland | Ohio | Oklahoma | Omaha | Ontario | Orange | Oregon | Orlando | Pennsylvania | Philadelphia | Phoenix | Pittsburgh | Plano | Portland | Port StLucie | Raleigh | Rhode Island | Roseville | Sacramento | Salem | San Antonio | San Diego | San Francisco | San Jose | Scottsdale | Seattle | Sioux falls | South Carolina | South Dakota | St Louis | Tampa | Tennessee | Texas | Thornton | Toledo | Tucson | Tulsa | Utah | Vancouver | Vermont | Virginia | West Virginia | Wichita | Wisconsin | Wyoming | Cost To Repair

All times are GMT -7. The time now is 09:01 PM.


Design by Vjacheslav Trushkin.
Powered by vBulletin® Version 3.6.5
Copyright ©2000 - 2009, Jelsoft Enterprises Ltd.
Search Engine Optimization by vBSEO 3.0.0 RC8
vB.Sponsors
All Rights Reserved. Hann Tech Marketing Link / InspectionNews.com / InspectionNews.net - No part of InspectionNews.net may be reproduced in any way, or by any means, without the prior written permission of InspectionNews.net. Use of any index or listing Software for the purpose of constructing a mailing list, creating promotional materials or producing a printed or electronic catalog of any kind is expressly forbidden without the prior written permission of InspectionNews.net - All text, graphics and design on InspectionNews.net is copyright by Hann Tech Marketing Links.
Ad Management by RedTyger