You are currently viewing InspectionNews as a guest which gives you limited access to view most discussions but not pictures. There are over 6,300 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, have access to post topics, communicate privately with other members, respond to polls, upload content and access many other special features. Registration is fast and simple so please, join InspectionNews today!
If you have any problems with the registration process or your account login, please contact us.
Why join InspectionNews? Read the Testimonials
|
|

06-18-2007, 01:57 PM
|
|
Member
|
|
Join Date: Mar 2007
Location: gone
Posts: 245
|
|
|
Electrical tape
.........
Last edited by Jeff Eastman : 12-20-2007 at 09:25 AM.
|
|

06-18-2007, 02:46 PM
|
|
Member
|
|
Join Date: Mar 2007
Location: Spring City/Surrounding Philadelphia area
Posts: 762
|
|
|
Re: Electrical tape
Jeff, how did you see the taped cable? Is it plainly exposed or did you need to remove a coverplate to see it?
|
|

06-18-2007, 04:57 PM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Santa Rosa, CA
Posts: 747
|
|
|
Re: Electrical tape
If the builder put it in writing, then he is accepting responsibility for it. You have made your recommendation.
__________________
The apostrophe troll.
|
|

06-19-2007, 07:02 AM
|
|
Member
|
|
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 7,644
|
|
|
Re: Electrical tape
Tell the builder to 'show me the code section which states that' ... or replace it.
|
|

06-19-2007, 07:06 AM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Duncanville, Tx
Posts: 1,086
|
|
|
Re: Electrical tape
Originally Posted by Jeff Eastman
My comment in my report:
"Electrical cable damaged and has improper repairs (taped) at upstairs left rear bedroom door entry topplate".
Builders' Comment:
"Electrical tape by code is considered insulation rated!"
Is this true??
Jeff,
While the builder should be able to back-up his statement... he won't. It will then be where he will challenge you with code to back-up your statement and finally become a pissing-contest that will eat up alot of your time and effort.
You saw, you identified, you reported.... time to move on.
Rich
__________________
"If con is the opposite of pro, is Congress the opposite of progress?"
Richard Rushing, HCRI
Duncanville, Tx.
|
|

06-19-2007, 07:12 AM
|
|
Member
|
|
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 7,644
|
|
|
Re: Electrical tape
Originally Posted by Richard Rushing
Jeff,
While the builder should be able to back-up his statement... he won't. It will then be where he will challenge you with code to back-up your statement
The BUILDER said "Electrical tape by code is considered insulation rated!"
Which is why I said "Tell the builder to 'show me the code section which states that' ... or replace it."
Jeff just stated it was damaged and needed repairs, he did not cite code - THE BUILDER DID, so let the builder back it up.
|
|

06-19-2007, 07:24 AM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Duncanville, Tx
Posts: 1,086
|
|
|
Re: Electrical tape
Jerry,
We are not saying anything different... just different ways.
The builder WON'T provide the code (he can't). He will say, "It been fine that way since Moby-Dick was a minnow and now this guy (Jeff) want's to say we can't do it this way?" "Why?"
Then the buyer turns to Jeff and says, "You can provide back up for that right?"
That's where it ALWAYS (by the builder or contractor) becomes a pissing contest because it eats up your time and energy that you should be spendig on doning another inspection, or writing a report or tickling ma-ma.
My point is that the buyer doesen't know anything. He is going to ask everyone to provide back-up for what they stated.... even though, the builder was the one who mentioned "code".
Rich
__________________
"If con is the opposite of pro, is Congress the opposite of progress?"
Richard Rushing, HCRI
Duncanville, Tx.
|
|

06-19-2007, 07:41 AM
|
|
Member
|
|
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 7,644
|
|
|
Re: Electrical tape
Originally Posted by Richard Rushing
The builder WON'T provide the code (he can't). He will say, "It been fine that way since Moby-Dick was a minnow and now this guy (Jeff) want's to say we can't do it this way?" "Why?"
Then the buyer turns to Jeff and says, "You can provide back up for that right?"
That's when Jeff gives his client 300.4, NEC (bold is mine).
- 300.4 Protection Against Physical Damage.
- - Where subject to physical damage, conductors shall be adequately protected.
(then it goes on being more specific about various things)
The fact of the matter is, if tape was needed, *they were NOT "adequately protected"*.
Then follow that with 'And the code does not tell you that you are allowed to repair damaged conductors.'
|
|
| Thread Tools |
Search this Thread |
|
|
|
Posting Rules
|
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts
HTML code is Off
|
|
|
| Thread |
Thread Starter |
Forum |
Replies |
Last Post |
| Electrical help needed |
william siegel |
Electrical Systems: Home Inspection and Commercial Inspection |
7 |
06-22-2007 06:30 PM |
| Air ducts/electrical cable |
RobertSmith |
Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection |
1 |
06-06-2007 08:52 PM |
| Electrical cable routing |
Jeff Eastman |
Electrical Systems: Home Inspection and Commercial Inspection |
2 |
06-05-2007 09:39 PM |
| electrical support |
John Arnold |
Electrical Systems: Home Inspection and Commercial Inspection |
3 |
05-25-2007 11:13 PM |
| Foil tape on vent pipe |
Jeff Eastman |
Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection |
5 |
05-18-2007 05:12 PM |
All times are GMT -7. The time now is 01:30 PM.
| | |
|