You are currently viewing InspectionNews as a guest which gives you limited access to view most discussions but not pictures. There are over 6,300 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, have access to post topics, communicate privately with other members, respond to polls, upload content and access many other special features. Registration is fast and simple so please, join InspectionNews today!

If you have any problems with the registration process or your account login, please contact us.

Why join InspectionNews? Read the Testimonials
Reply
 
LinkBack Thread Tools Search this Thread
  #1 (permalink)  
Old 04-02-2007, 12:52 AM
Tim Moreira's Avatar
Tim Moreira Tim Moreira is offline
Member
 
Join Date: Mar 2007
Location: New Port Richey, Fl
Posts: 446
From the old board, Knob and Tube Wiring
who will?

posted March 14, 2007 06:04 AM
Had an "electricion" just call me in reguards my report. He was upset that I stated in my report presence of live know and tube wiring, and I stated this as a hazzard and saftey concern. He kept telling me that there was no code that states that this is a hazzard and he stated that according to engineers the knob and tube is the safest and best system out there if installed properly. My statement to him was that I did fine live K&T wiring and noted it in my report and that I also stated the safety hazzard and it should be replaced by a qualified electrician. He said that I was scareing the customer and I shouild not mention this much less bring it to the customers attention.
What I am asking for is 2 fold.
1 Am I not right in stating this in my report as I said?
2 Where is there info that I can givve to my customer to better explain the hazzards of K&T from another source other than my and or the "electrician's" word.
Any thing would help.
Also Is there a web site that I can acess on the electric codes? Thanks ------------------
Brian Kelly
Kelly Home Inspections
Reply With Quote
  #2 (permalink)  
Old 04-02-2007, 07:03 AM
william siegel's Avatar
william siegel william siegel is offline
Member
 
Join Date: Mar 2007
Location: Miami, Florida
Posts: 114
Re: From the old board, Knob and Tube Wiring
Tim,

Citizens (and I am sure others) will not accept knob and tube wiring. They want it replaced.
Reply With Quote
  #3 (permalink)  
Old 04-02-2007, 08:17 AM
Kevin Luce's Avatar
Kevin Luce Kevin Luce is offline
Member
 
Join Date: Mar 2007
Location: Highland, IN
Posts: 369
Re: From the old board, Knob and Tube Wiring
Quote:
Originally Posted by Tim Moreira View Post
My statement to him was that I did fine live K&T wiring and noted it in my report and that I also stated the safety hazzard and it should be replaced by a qualified electrician.
Do you noticed something specifically wrong with the K&T?

In this area, most insurance companies wants the K&T wiring approved by a licensed electrician. And guess what, most if not all electrician will not put in writing that the wiring is fine and the K&T gets changed.

You many want to do what I did and call around to the different insurance companies and ask what happens if a house has K&T wiring.
Reply With Quote
  #4 (permalink)  
Old 04-02-2007, 09:37 PM
James Allen James Allen is offline
Member
 
Join Date: Mar 2007
Location: Kansas City MO
Posts: 2
Re: From the old board, Knob and Tube Wiring
In our part of the country Tim, there is a lot of Knob and Tube wiring. As with all old stuff, the question is.....Is it still working as intended? If the system has been modified improperly, it gets called out. If is is covered with insulation in the attic....it gets called out. If it is frayed and coming apart...guess what? It gets called out. It is not that it is a bad system. It is just freaken old.

When I note it in my report, I note that this is an old system (not a bad system) and may have age and modification defects that are beyond the scope of this inspection to investigate. I recommend that the system be reviewed by an electrician.
__________________
James P. Allen
Sweet Home Inspection, Inc
"Saving the world. One house at a time"
Reply With Quote
  #5 (permalink)  
Old 04-02-2007, 10:33 PM
Tim Moreira's Avatar
Tim Moreira Tim Moreira is offline
Member
 
Join Date: Mar 2007
Location: New Port Richey, Fl
Posts: 446
Re: From the old board, Knob and Tube Wiring
Note: Not my thread, copied from the old board.

K&T needs to be replaced in my opinion.
Reply With Quote
Are inspection referrals from past clients important to you?
If so, click here to get even more referrals!
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
From the old board, Abandon Wiring Tim Moreira Electrical Systems: Home Inspection and Commercial Inspection 0 04-02-2007 12:48 AM


All times are GMT -7. The time now is 01:16 PM.


Design by Vjacheslav Trushkin.
Powered by vBulletin® Version 3.6.5
Copyright ©2000 - 2008, Jelsoft Enterprises Ltd.
Search Engine Optimization by vBSEO 3.0.0 RC8
vB.Sponsors
All Rights Reserved. Hann Tech Marketing Link / InspectionNews.com / InspectionNews.net - No part of InspectionNews.net may be reproduced in any way, or by any means, without the prior written permission of InspectionNews.net. Use of any index or listing Software for the purpose of constructing a mailing list, creating promotional materials or producing a printed or electronic catalog of any kind is expressly forbidden without the prior written permission of InspectionNews.net - All text, graphics and design on InspectionNews.net is copyright by Hann Tech Marketing Links.
Ad Management by RedTyger