You are currently viewing InspectionNews as a guest which gives you limited access to view most discussions but not pictures. There are over 6,300 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, have access to post topics, communicate privately with other members, respond to polls, upload content and access many other special features. Registration is fast and simple so please, join InspectionNews today!

If you have any problems with the registration process or your account login, please contact us.

Why join InspectionNews? Read the Testimonials
Reply
 
LinkBack Thread Tools Search this Thread
  #1 (permalink)  
Old 07-23-2007, 06:51 PM
Michael Thomas's Avatar
Michael Thomas Michael Thomas is offline
Member
 
Join Date: Mar 2007
Location: Chicago, IL
Posts: 1,155
Load side panel close to service equipment
"Load side" panel 18" from service equipment, connected to it by conduit. Both neutral buses bonded to panel. Is there some sort of exception that makes these both part of the "service equipment" due to their proximity?
Attached Images
File Type: jpg SD1.jpg (17.5 KB, 23 views)
File Type: jpg SD2.jpg (30.2 KB, 25 views)
File Type: jpg SD3.jpg (45.0 KB, 28 views)
File Type: jpg SD4.jpg (43.9 KB, 23 views)
Reply With Quote
Are inspection referrals from past clients important to you? If so, click here to get even more referrals!
  #2 (permalink)  
Old 07-23-2007, 08:36 PM
Jerry Peck Jerry Peck is offline
Member
 
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 7,644
Re: Load side panel close to service equipment
Nope.
__________________
Jerry Peck, Construction / Litigation Consultant
Construction Litigation Consultants, LLC ( www.ConstructionLitigationConsultants.com )
Reply With Quote
  #3 (permalink)  
Old 07-23-2007, 09:24 PM
Michael Thomas's Avatar
Michael Thomas Michael Thomas is offline
Member
 
Join Date: Mar 2007
Location: Chicago, IL
Posts: 1,155
Re: Load side panel close to service equipment
Thanks. For various reasons, I don't want to call out *anything* that could come back to bite me on this inspection.
Reply With Quote
  #4 (permalink)  
Old 07-23-2007, 09:39 PM
Phillip Stojanik's Avatar
Phillip Stojanik Phillip Stojanik is offline
Member
 
Join Date: Mar 2007
Location: Houston, Texas
Posts: 216
Re: Load side panel close to service equipment
Quote:
Originally Posted by Michael Thomas View Post
Thanks. For various reasons, I don't want to call out *anything* that could come back to bite me on this inspection.
Now the above is an extremely dangerous quote Michael because *anything* you call out could come back to bite you on this (or any other) inspection!

Its just part of putting your pants on one leg at a time and going to work each morning as a home inspector within our litigious society.
Reply With Quote
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Wire splices in service equipment panel Jeff Eastman Electrical Systems: Home Inspection and Commercial Inspection 13 12-10-2007 01:22 PM
SE Panel In Close Closet OK K Robertson Electrical Systems: Home Inspection and Commercial Inspection 16 10-04-2007 01:28 PM
How close can a switch be to a hydro-therapy equipment? M Kelekci Plumbing System: Home Inspection and Commercial Inspection 6 07-22-2007 07:40 PM
Service panel question Jim McClendon Electrical Systems: Home Inspection and Commercial Inspection 12 05-21-2007 06:19 PM
2 Wire Load Side Fuse Panel Michael Thomas Electrical Systems: Home Inspection and Commercial Inspection 2 04-12-2007 03:22 PM


All times are GMT -7. The time now is 01:22 PM.


Design by Vjacheslav Trushkin.
Powered by vBulletin® Version 3.6.5
Copyright ©2000 - 2008, Jelsoft Enterprises Ltd.
Search Engine Optimization by vBSEO 3.0.0 RC8
vB.Sponsors
All Rights Reserved. Hann Tech Marketing Link / InspectionNews.com / InspectionNews.net - No part of InspectionNews.net may be reproduced in any way, or by any means, without the prior written permission of InspectionNews.net. Use of any index or listing Software for the purpose of constructing a mailing list, creating promotional materials or producing a printed or electronic catalog of any kind is expressly forbidden without the prior written permission of InspectionNews.net - All text, graphics and design on InspectionNews.net is copyright by Hann Tech Marketing Links.
Ad Management by RedTyger