Re: Protection of wiring in the attic
M,
From the 03 IRC.
E3702.2.1 Across structural members.
Where run across the top of floor joists, or run within 7 feet (2134 mm) of floor or floor joists across the face of rafters or studding, in attics and roof spaces that are provided with access, the cable shall be protected by substantial guard strips that are at least as high as the cable. Where such spaces are not provided with access by permanent stairs or ladders, protection shall only be required within 6 feet (1829 mm) of the nearest edge of the attic entrance.
I'm sure this is in the NEC too somewhere. Don't have the NEC infront of me right now to quote it.
|