You are currently viewing InspectionNews as a guest which gives you limited access to view most discussions but not pictures. There are over 6,300 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, have access to post topics, communicate privately with other members, respond to polls, upload content and access many other special features. Registration is fast and simple so please, join InspectionNews today!

If you have any problems with the registration process or your account login, please contact us.

Why join InspectionNews? Read the Testimonials
Reply
 
LinkBack Thread Tools Search this Thread
  #1 (permalink)  
Old 09-29-2007, 07:48 AM
Jeff Eastman Jeff Eastman is offline
Member
 
Join Date: Mar 2007
Location: gone
Posts: 245
outlets next to sink
........

Last edited by Jeff Eastman : 12-11-2007 at 06:15 PM.
Reply With Quote
Are inspection referrals from past clients important to you? If so, click here to get even more referrals!
  #2 (permalink)  
Old 09-29-2007, 09:44 AM
Richard Rushing's Avatar
Richard Rushing Richard Rushing is offline
Member
 
Join Date: Mar 2007
Location: Duncanville, Tx
Posts: 1,086
Re: outlets next to sink
I think if you ask the question, you know the answer...

Think about it. The lack of outlets will cause a lazy occupant to take the easy way out by installing extension cords or overloading gang plugs at other locations and running cords to this area.

The use of extension cords is meant to be a short term use item and not a permanent wiring condition. This represents a potential fire hazard that may or may-not take place when the occupants are present-- Yikes!!

rr
__________________
"If con is the opposite of pro, is Congress the opposite of progress?"
Richard Rushing, HCRI
Duncanville, Tx.
Reply With Quote
  #3 (permalink)  
Old 09-29-2007, 11:39 AM
Jerry Peck Jerry Peck is online now
Member
 
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 6,945
Re: outlets next to sink
No receptacles are required for bathrooms, other than in dwelling units, and you stated that was commercial.

More importantly, for commercial, do those bathroom meet ADA sizes (regardless of other requirements, which should also be looked at).
__________________
Jerry Peck, Construction / Litigation Consultant
Construction Litigation Consultants, LLC ( www.ConstructionLitigationConsultants.com )
EastWestData (www.EastWestData.com )
Reply With Quote
  #4 (permalink)  
Old 10-05-2007, 03:40 PM
John Steinke's Avatar
John Steinke John Steinke is offline
Member
 
Join Date: Mar 2007
Location: Reno, Nv.
Posts: 115
Re: outlets next to sink
Jeff, being 'adjacent to A/C' has no bearing on whether they need to be GFCI protected or not.

GFCI requirements are based upon the equipment location. While a case may be made for rooftop receptacles, and even crawl space receptacles, to be GFCI ... there is no such requirement for such equipment in mechanical rooms or attics.
Reply With Quote
Are inspection referrals from past clients important to you? If so, click here to get even more referrals!
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
difficult outlets Matt Fellman Electrical Systems: Home Inspection and Commercial Inspection 4 09-27-2007 12:25 PM
One GFCI by sink, one not? Dave Hill Electrical Systems: Home Inspection and Commercial Inspection 19 08-07-2007 07:48 PM
Outlets under soffits John Stephenson Electrical Systems: Home Inspection and Commercial Inspection 3 06-02-2007 03:08 PM
Testing GFCI Outlets Roger Kautz Electrical Systems: Home Inspection and Commercial Inspection 10 04-30-2007 06:30 AM
CPSC Recall: Floor Electrical Outlets Brian Hannigan Electrical Systems: Home Inspection and Commercial Inspection 0 04-18-2007 11:29 AM


All times are GMT -7. The time now is 04:58 PM.


Design by Vjacheslav Trushkin.
Powered by vBulletin® Version 3.6.5
Copyright ©2000 - 2008, Jelsoft Enterprises Ltd.
Search Engine Optimization by vBSEO 3.0.0 RC8
vB.Sponsors
All Rights Reserved. Hann Tech Marketing Link / InspectionNews.com / InspectionNews.net - No part of InspectionNews.net may be reproduced in any way, or by any means, without the prior written permission of InspectionNews.net. Use of any index or listing Software for the purpose of constructing a mailing list, creating promotional materials or producing a printed or electronic catalog of any kind is expressly forbidden without the prior written permission of InspectionNews.net - All text, graphics and design on InspectionNews.net is copyright by Hann Tech Marketing Links.
Ad Management by RedTyger