You are currently viewing InspectionNews as a guest which gives you limited access to view most discussions but not pictures. There are over 6,300 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, have access to post topics, communicate privately with other members, respond to polls, upload content and access many other special features. Registration is fast and simple so please, join InspectionNews today!

If you have any problems with the registration process or your account login, please contact us.

Why join InspectionNews? Read the Testimonials
Reply
 
LinkBack Thread Tools Search this Thread
  #1 (permalink)  
Old 09-29-2007, 12:21 PM
Jeff Eastman Jeff Eastman is offline
Member
 
Join Date: Mar 2007
Location: gone
Posts: 245
A/C Disconnect boxe:
..........

Last edited by Jeff Eastman : 12-11-2007 at 06:12 PM.
Reply With Quote
Home inspection
  #2 (permalink)  
Old 09-29-2007, 01:44 PM
Jerry Peck Jerry Peck is online now
Member
 
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 7,035
Re: A/C Disconnect boxe:
While I don't like that, there is no switch or overcurrent device in there, so it's okay.
__________________
Jerry Peck, Construction / Litigation Consultant
Construction Litigation Consultants, LLC ( www.ConstructionLitigationConsultants.com )
EastWestData (www.EastWestData.com )
Reply With Quote
  #3 (permalink)  
Old 09-29-2007, 01:46 PM
Billy Stephens's Avatar
Billy Stephens Billy Stephens is offline
Member
 
Join Date: Aug 2007
Location: Memphis TN.
Posts: 1,496
Re: A/C Disconnect boxe:
Jeff,

See Mr. Peck above.
__________________
It Might have Choked Artie But it ain't gone'a choke Stymie!
Billy J. Stephens HI Service
Memphis TN.
Reply With Quote
  #4 (permalink)  
Old 09-29-2007, 01:53 PM
Billy Stephens's Avatar
Billy Stephens Billy Stephens is offline
Member
 
Join Date: Aug 2007
Location: Memphis TN.
Posts: 1,496
Re: A/C Disconnect boxe:
Mr Peck,

If there are fuse's in the disconnect then it would be an over current device.
__________________
It Might have Choked Artie But it ain't gone'a choke Stymie!
Billy J. Stephens HI Service
Memphis TN.
Reply With Quote
  #5 (permalink)  
Old 09-29-2007, 07:16 PM
Jerry Peck Jerry Peck is online now
Member
 
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 7,035
Re: A/C Disconnect box:
Quote:
Originally Posted by Billy Stephens View Post
Mr Peck,

If there are fuse's in the disconnect then it would be an over current device.
You are, of course, correct *IF fused*, however, that photo looked like it was just a non-fused pull out disconnect. Meaning NO overcurrent protection.
__________________
Jerry Peck, Construction / Litigation Consultant
Construction Litigation Consultants, LLC ( www.ConstructionLitigationConsultants.com )
EastWestData (www.EastWestData.com )
Reply With Quote
  #6 (permalink)  
Old 09-29-2007, 07:20 PM
Jerry Peck Jerry Peck is online now
Member
 
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 7,035
Re: A/C Disconnect box:
Quote:
Originally Posted by dan orourke View Post
Should not those whites be labeled hot?
Dan,

Those whites look like the neutrals of the black & white circuit passing through. At least that's what I took them to be.

Which is one of the very reasons the whites are required to be "permanently reidentified by painting" or other effective (permanent) means *IF* they are part of a 240 volt circuit and not the neutrals for a 120 volt circuit.

You'd need to ask Jeff if he checked that as we cannot tell from the photo.
__________________
Jerry Peck, Construction / Litigation Consultant
Construction Litigation Consultants, LLC ( www.ConstructionLitigationConsultants.com )
EastWestData (www.EastWestData.com )
Reply With Quote
  #7 (permalink)  
Old 09-30-2007, 06:57 AM
Billy Stephens's Avatar
Billy Stephens Billy Stephens is offline
Member
 
Join Date: Aug 2007
Location: Memphis TN.
Posts: 1,496
Re: A/C Disconnect box:
Quote:
Originally Posted by Jerry Peck View Post
however, that photo looked like it was just a non-fused pull out disconnect. Meaning NO overcurrent protection.
Mr. Peck,

Thanks. I can see the panel does not look deep enough.
__________________
It Might have Choked Artie But it ain't gone'a choke Stymie!
Billy J. Stephens HI Service
Memphis TN.
Reply With Quote
Home inspection
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
HVAC disconnect M Kelekci Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection 4 07-06-2007 08:04 PM
FPE main disconnect Paul Kondzich Electrical Systems: Home Inspection and Commercial Inspection 2 06-20-2007 05:52 PM
AHU disconnect Jerry Peck Electrical Systems: Home Inspection and Commercial Inspection 5 05-16-2007 07:34 AM
A/C disconnect location Jeff Eastman Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection 6 05-08-2007 05:13 PM
a/c disconnect Martin lehman Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection 6 04-03-2007 11:48 PM


All times are GMT -7. The time now is 09:19 AM.


Design by Vjacheslav Trushkin.
Powered by vBulletin® Version 3.6.5
Copyright ©2000 - 2008, Jelsoft Enterprises Ltd.
Search Engine Optimization by vBSEO 3.0.0 RC8
vB.Sponsors
All Rights Reserved. Hann Tech Marketing Link / InspectionNews.com / InspectionNews.net - No part of InspectionNews.net may be reproduced in any way, or by any means, without the prior written permission of InspectionNews.net. Use of any index or listing Software for the purpose of constructing a mailing list, creating promotional materials or producing a printed or electronic catalog of any kind is expressly forbidden without the prior written permission of InspectionNews.net - All text, graphics and design on InspectionNews.net is copyright by Hann Tech Marketing Links.
Ad Management by RedTyger