You are currently viewing InspectionNews as a guest which gives you limited access to view most discussions but not pictures. There are over 6,300 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, have access to post topics, communicate privately with other members, respond to polls, upload content and access many other special features. Registration is fast and simple so please, join InspectionNews today!

If you have any problems with the registration process or your account login, please contact us.

Why join InspectionNews? Read the Testimonials
Reply
 
LinkBack Thread Tools Search this Thread
  #1 (permalink)  
Old 10-21-2007, 09:51 AM
Jim Robinson's Avatar
Jim Robinson Jim Robinson is offline
Member
 
Join Date: Mar 2007
Location: New Mexico
Posts: 341
Mobile Home SEC
Sparky said the SEC on the ground was code compliant. I don't care that much, as it is a no brainer to me that the cord should be protected from physical damage. I just wanted to clarify if that is indeed compliant for a mobile home or if it would be required to be protected. Does anyone know the current code for mobile home SEC? I know they have their own codes on a lot of things.

The seller is pissed because it didn't sell, so he fired off a letter to me stating all of the "mistakes" on my report.
Attached Images
File Type: jpg 0108.JPG (120.5 KB, 100 views)
__________________
Jim Robinson
New Mexico, USA
Reply With Quote
Home inspection
  #2 (permalink)  
Old 10-21-2007, 10:52 AM
Scott Patterson's Avatar
Scott Patterson Scott Patterson is offline
Member
 
Join Date: Mar 2007
Location: Spring Hill (Nashville), TN
Posts: 1,751
Re: Mobile Home SEC
In most areas manufactured homes fall under the Department of Transportation. HUD has a good amount of information on them, and I bet that you could support your findings with the NEC.

Me, I would not even bother replying to the seller.
__________________
Scott Patterson
Spring Hill, TN
http://www.traceinspections.com
Reply With Quote
  #4 (permalink)  
Old 10-21-2007, 06:44 PM
Gunnar Alquist's Avatar
Gunnar Alquist Gunnar Alquist is online now
Member
 
Join Date: Mar 2007
Location: Santa Rosa, CA
Posts: 747
Re: Mobile Home SEC
To the best of my knowledge, it is acceptable for 50 amps or less. Greater than 50 amps needs to be in a conduit. However, as a consultant, you certainly have the right and responsibility to recommend more than the bare minimum requirement. A rubber cord lying on the ground is subject to physical damage and protecting the cord is a really good idea.
__________________
The apostrophe troll.
Reply With Quote
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
YOUR PLACE TO CALL HOME: Is a home inspection worth the money? - Suburban Journals Brian Hannigan Inspection News From Around The Net 0 09-30-2007 04:27 PM
Mobile home ceiling material????? Brian E Kelly Building Interior: Home Inspection and Commercial Inspection 23 08-02-2007 12:52 PM
Miller mobile home furnace dating Brian E Kelly Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection 0 07-31-2007 05:53 PM
Mobile home owners face new inspection - Chillicothe Gazette Brian Hannigan Inspection News From Around The Net 0 06-21-2007 10:41 AM


All times are GMT -7. The time now is 12:58 PM.


Design by Vjacheslav Trushkin.
Powered by vBulletin® Version 3.6.5
Copyright ©2000 - 2008, Jelsoft Enterprises Ltd.
Search Engine Optimization by vBSEO 3.0.0 RC8
vB.Sponsors
All Rights Reserved. Hann Tech Marketing Link / InspectionNews.com / InspectionNews.net - No part of InspectionNews.net may be reproduced in any way, or by any means, without the prior written permission of InspectionNews.net. Use of any index or listing Software for the purpose of constructing a mailing list, creating promotional materials or producing a printed or electronic catalog of any kind is expressly forbidden without the prior written permission of InspectionNews.net - All text, graphics and design on InspectionNews.net is copyright by Hann Tech Marketing Links.
Ad Management by RedTyger