InspectionNews - Home Inspection



Registration is FREE!... and will get rid of this top message

Welcome to InspectionNews.net.

You are currently viewing InspectionNews as a guest which gives you limited access to view some discussions but none of the pictures.

There are over 9,970 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, post new topics or reply to others, communicate privately with other members, respond to polls, upload content and access many other special features.

Registration is FREE for you because the sponsors pay your way. Please visit the sponsors often and let them know that you found them on InspectionNews!

Registration is FREE, fast and easy so please, join InspectionNews today!

Why join InspectionNews? Read the Testimonials

Looking for Education? We recommend Casey, O'Malley and Associates
Home and Commercial Inspection Education

If you have any problems with the registration process or your account login, please contact us.

Reply
 
LinkBack Thread Tools Search this Thread
  #1 (permalink)  
Old 03-12-2008, 10:37 AM
Matthew Barnicle Matthew Barnicle is offline
Member
 
Join Date: Mar 2007
Location: Tampa, Fl
Posts: 135
Service Ampacity
What would you rate this service at?

1/0 Copper Service Entrance Conductors
Service Equipment panel had 3 Breakers for means of main disconnect.
100A to house panel
30A to pool panel
60A to HVAC package unit panel

Service Equip. Panel had no ampacity rating visible on label.
Reply With Quote
  #2 (permalink)  
Old 03-12-2008, 12:02 PM
Raymond Wand Raymond Wand is offline
Member
 
Join Date: Feb 2008
Location: Caledon, Ontario
Posts: 1,129
Re: Service Ampacity
If its 1/0 its rated upto 150 amps.
__________________
The value of experience is not in seeing much, but in seeing wisely. - Sir William Osler 1905
Reply With Quote
  #3 (permalink)  
Old 03-14-2008, 08:44 AM
Jon Randolph Jon Randolph is offline
Member
 
Join Date: Mar 2007
Location: Indianapolis, Indiana
Posts: 353
Re: Service Ampacity
The rating that you give the service should be the smaller of the SEC, panel rating or main isconnect rating. Make sure that you are looking at the lines from the mast to the pole also and not just from the meter to the main.

Without a legible lable on the panel, I would state that I could not verify the size of the service and state why.


Make sure that you do not rate it at more than it is capable of or you may be upgrading it youself.
__________________
Integrity Inspection Service, LLC
www.irsindy.com
(317) 345-1828
Reply With Quote
  #4 (permalink)  
Old 03-14-2008, 11:05 AM
Lanny Freng's Avatar
Lanny Freng Lanny Freng is offline
Member
 
Join Date: Jun 2007
Location: Farmington, MN
Posts: 44
Re: Service Ampacity
Dont forget to take into account the meter as well, Older ones are not rated as high as newer ones. somewhat of a rule of thumb. round = 60 amp, square = 100 amp, rectangular = 150+
__________________
Lanny Freng
Inspection WerX
"Get the Best of US before your new home gets the best of YOU!"
Reply With Quote
  #5 (permalink)  
Old 03-14-2008, 01:08 PM
Jerry Peck's Avatar
Jerry Peck Jerry Peck is offline
Member
 
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 14,293
Re: Service Ampacity
Quote:
Originally Posted by Jon Randolph View Post
The rating that you give the service should be the smaller of the SEC, panel rating or main isconnect rating.

Except, as in this case, when there are multiple main disconnects, then the smaller of the service entrance conductor rating or the combined rating of the multiple mains. While multiple mains cannot be combined to get a true rating, they can be combined to get a 'maximum rating', and if that is smaller than the service entrance conductors, then that 'maximum rating' would be the service size, i.e., being the smaller of the two.

In the case stated above:
1/0 Copper Service Entrance Conductors
Service Equipment panel had 3 Breakers for means of main disconnect.
100A to house panel
30A to pool panel
60A to HVAC package unit panel

The 1/0 copper is rated for 175 amps, the 3 multiple mains add up to 190 amps, thus the service size is 175 amps.
__________________
Jerry Peck, Construction / Litigation Consultant
Construction Litigation Consultants, LLC ( www.ConstructionLitigationConsultants.com )
www.AskCodeMan.com
Reply With Quote
  #6 (permalink)  
Old 03-14-2008, 07:06 PM
Eric Barker's Avatar
Eric Barker Eric Barker is offline
Member
 
Join Date: Mar 2007
Location: Barrington, IL
Posts: 515
Re: Service Ampacity
Around here you cannot take into account the size of the overhead drop. First of all, the utility can put in whatever gauge they want up to the house and no one can say boo about it. Second, the overhead conductors are surrounded by air, an insulator not found around the conductors in the home wiring. Therefore, "standard" ratings do not apply.
__________________
Eric Barker
Moraine Woods Consulting, Inc.
Barrington, IL
Reply With Quote
  #7 (permalink)  
Old 03-14-2008, 08:13 PM
Jerry Peck's Avatar
Jerry Peck Jerry Peck is offline
Member
 
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 14,293
Re: Service Ampacity
Quote:
Originally Posted by Eric Barker View Post
Around here you cannot take into account the size of the overhead drop.

Eric,

Should not be concerned with the size of the overhead service drop anywhere (unless it's #10 wire ).

We are talking about the "service entrance conductors", not the "over head service drop conductors".
__________________
Jerry Peck, Construction / Litigation Consultant
Construction Litigation Consultants, LLC ( www.ConstructionLitigationConsultants.com )
www.AskCodeMan.com
Reply With Quote
IC Home Inspection Report Writing
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Seperate service to outbuilding serves circuits in main building with own service ... Michael Thomas Electrical Systems: Home Inspection and Commercial Inspection 3 02-17-2008 07:44 AM
This is 3 phase service, right? Matthew Barnicle Electrical Systems: Home Inspection and Commercial Inspection 25 12-18-2007 06:17 PM
Service conduit bonding at service equipment Michael Thomas Electrical Systems: Home Inspection and Commercial Inspection 0 08-07-2007 06:59 AM
Service Panel David Banks Electrical Systems: Home Inspection and Commercial Inspection 42 08-03-2007 09:27 AM
Welcome From F.I.R.E. Service Dale W. Feb Introductions By New Members 0 04-04-2007 06:22 PM

Alabama | Alaska | Arizona | Atlanta | Aurora | Austin | Baltimore | Boston | California | Cambridge | Cape Coral | Chandler | Charlotte | Chicago | Cincinnati | Clarksville | Cleveland | Colorado | Columbus | Connecticut | Dallas | Delaware | Denver | Detroit | Durham | El Paso | Eugene | Florida | Fort Worth | Fresno | Georgia | Gilbert | Hawaii | Henderson | Houston | Huntsville | Idaho | Illinois | Indiana | Indianapolis | Irvine | Jacksonville | Joliet | Kansas City | Knoxville | Lancaster | Las Vegas | Los Angeles | Louisiana | Louisville | Maine | Maryland | Massachusetts | Memphis | Mesa | Miami | Michigan | Milwaukee | Minneapolis | Minnesota | Miramar | Mississippi | Missouri | Montana | Nashville | Nebraska | Nevada | New Hampshire | New Jersey | New Mexico | New York | North Carolina | North Dakota | Oakland | Ohio | Oklahoma | Omaha | Ontario | Orange | Oregon | Orlando | Pennsylvania | Philadelphia | Phoenix | Pittsburgh | Plano | Portland | Port StLucie | Raleigh | Rhode Island | Roseville | Sacramento | Salem | San Antonio | San Diego | San Francisco | San Jose | Scottsdale | Seattle | Sioux falls | South Carolina | South Dakota | St Louis | Tampa | Tennessee | Texas | Thornton | Toledo | Tucson | Tulsa | Utah | Vancouver | Vermont | Virginia | West Virginia | Wichita | Wisconsin | Wyoming | Cost To Repair

All times are GMT -7. The time now is 02:32 AM.


Design by Vjacheslav Trushkin.
Powered by vBulletin® Version 3.6.5
Copyright ©2000 - 2009, Jelsoft Enterprises Ltd.
Search Engine Optimization by vBSEO 3.0.0 RC8
vB.Sponsors
All Rights Reserved. Hann Tech Marketing Link / InspectionNews.com / InspectionNews.net - No part of InspectionNews.net may be reproduced in any way, or by any means, without the prior written permission of InspectionNews.net. Use of any index or listing Software for the purpose of constructing a mailing list, creating promotional materials or producing a printed or electronic catalog of any kind is expressly forbidden without the prior written permission of InspectionNews.net - All text, graphics and design on InspectionNews.net is copyright by Hann Tech Marketing Links.
Ad Management by RedTyger