You are currently viewing InspectionNews as a guest which gives you limited access to view most discussions but not pictures. There are over 6,300 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, have access to post topics, communicate privately with other members, respond to polls, upload content and access many other special features. Registration is fast and simple so please, join InspectionNews today!
If you have any problems with the registration process or your account login, please contact us.
Why join InspectionNews? Read the Testimonials
|
|

03-15-2008, 12:12 PM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Myrtle Beach, South Carolina
Posts: 281
|
|
|
De-rating Revisited
Would you say that this bundle should be de-rated and/or appropriate repairs be conducted by a licensed and qualified electrician?
I already called out the missing knockout.
And, while I'm at it.... there was an addition to this house... a patio was enclosed.... some electrical was run.... all other breakers being original.... all squareD.... this one caught my eye.... could it be one of those bogus SquareD breakers?
Last edited by Victor DaGraca : 03-15-2008 at 12:19 PM.
Reason: after thought
|
|

03-15-2008, 12:19 PM
|
|
Member
|
|
Join Date: Mar 2007
Location: Philadelphia PA
Posts: 1,185
|
|
|
Re: De-rating Revisited
Originally Posted by Victor DaGraca
Would you say that this bundle should be de-rated and/or appropriate repairs be conducted by a licensed and qualified electrician?
I already called out the missing knockout.
Everything shouldn't be stuffed through together like that, but for de-rating they have to be bundled for at least 24 inches, if memory serves.
|
|

03-15-2008, 12:27 PM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Myrtle Beach, South Carolina
Posts: 281
|
|
|
Re: De-rating Revisited
Thanks John.... now that you mentioned the 24"......
|
|

03-15-2008, 12:56 PM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Santa Rosa, CA
Posts: 596
|
|
|
Re: De-rating Revisited
I think that you will also find that strain relief clamps are required, not a bushing.
__________________
What is the circumference of a moose?
|
|

03-15-2008, 01:40 PM
|
|
Member
|
|
Join Date: Mar 2007
Location: Southborough, MA
Posts: 912
|
|
|
Re: De-rating Revisited
__________________
Dave
|
|

03-16-2008, 06:54 AM
|
|
Member
|
|
Join Date: Mar 2007
Location: Southborough, MA
Posts: 912
|
|
|
Re: De-rating Revisited
Originally Posted by Victor DaGraca
I had the same problem looking at your pics. Thats why I posted the link with no comment.  Good luck.
__________________
Dave
|
|

03-16-2008, 09:28 AM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Hamlin, New York
Posts: 76
|
|
|
Re: De-rating Revisited
Victor,
I believe your breaker is one of Square D's new Homeline series and is made to fit other panel boxes as well as there own.
Lee
|
|

03-16-2008, 08:27 PM
|
|
Member
|
|
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 6,521
|
|
|
Re: De-rating Revisited
Originally Posted by Gunnar Alquist
I think that you will also find that strain relief clamps are required, not a bushing.
Yep.
So, even if they are like that for less than 24" ... they are *STILL* "wrong". 
|
|

03-16-2008, 08:58 PM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Myrtle Beach, South Carolina
Posts: 281
|
|
|
Re: De-rating Revisited
Jerry;
Even though I can't ascertain that those wires do or don't run like that for 24" I'd still "assume" (dangerous word there) that the amount of wires and their proximity within that orifice would produce excessive heat build up.
Of course I'm not an electrician or an engineer and even the IRC does not specifically dis-allow (prohibit) that specific scenario, that being said.... if it looks like a duck......
|
|

03-16-2008, 09:22 PM
|
|
Member
|
|
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 6,521
|
|
|
Re: De-rating Revisited
Originally Posted by Victor DaGraca
Even though I can't ascertain that those wires do or don't run like that for 24"
That's why I quoted Gunnar (and am doing so again).
Originally Posted by Gunnar Alquist
I think that you will also find that strain relief clamps are required, not a bushing.
Forget about the 24" and derating, go on to something which is plainly visible.
Correct THAT, and, by virtue of correcting that, you are also correcting the un-verifiable 24" ... whether or not if it - er - "was" (as in "past tense") 24" or greater, or less, no longer matters.
|
|

03-17-2008, 04:28 AM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Myrtle Beach, South Carolina
Posts: 281
|
|
|
Re: De-rating Revisited
You know..... sometimes things in plain sight make a dope outa me.... All along I thought Gunnar was refering to the lone wire on the left coming through the bushing. (no strain relief clamp)
THEN.... Outa the blue.......
Thanks Jerry
Thanks Gunnar
Thanks to all...
|
|

03-17-2008, 02:37 PM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Myrtle Beach, South Carolina
Posts: 281
|
|
|
Re: De-rating Revisited
Ok... I received a reply from Schneider Electric. Here it is.
Lee .... Looks like you hit it.
Dear Victor DaGraca:
Thank you for your internet inquiry. I asked the plant and corporate offices to look at this picture. Neither can confirm or deny that the breaker shown on that picture is a counterfeit breaker. From the corporate people, they have said there have been no known instances at this time of counterfeit HOM, or Homeline breakers.
To verify for sure, we would need to have the product returned to us for inspection by one of our engineers. You may contact a local field sales office to initiate this process.
To find the Square D/Schneider Electric Sales Office nearest you, click the following link:
http://ecatalog.squared.com/ssearch/
Please feel free to contact us, should you have any further questions.
Regards,
Kevin McDonald.
Product Support Specialist.
Schneider Electric
1-888-778-2733
|
|
| Thread Tools |
Search this Thread |
|
|
|
Posting Rules
|
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts
HTML code is Off
|
|
|
| Thread |
Thread Starter |
Forum |
Replies |
Last Post |
| Rating inversion |
Richard Stanley |
General Chit Chat: Home Inspectors & Commercial Inspectors |
2 |
09-10-2007 01:47 PM |
| SEER rating |
Fritz Kelly |
Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection |
3 |
07-31-2007 07:07 PM |
| Main breaker rating |
RobertSmith |
Electrical Systems: Home Inspection and Commercial Inspection |
4 |
06-01-2007 11:48 AM |
| Help Please - Revisited |
Jim Dull |
Building Envelope: Home Inspection and Commercial Inspection |
16 |
04-20-2007 10:36 PM |
| SEER rating |
Buster Foster |
Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection |
9 |
04-08-2007 03:46 PM |
All times are GMT -7. The time now is 06:05 PM.
| | |
|