InspectionNews - Home Inspection



Registration is FREE!... and will get rid of this top message

Welcome to InspectionNews.net.

You are currently viewing InspectionNews as a guest which gives you limited access to view some discussions but none of the pictures.

There are over 9,970 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, post new topics or reply to others, communicate privately with other members, respond to polls, upload content and access many other special features.

Registration is FREE for you because the sponsors pay your way. Please visit the sponsors often and let them know that you found them on InspectionNews!

Registration is FREE, fast and easy so please, join InspectionNews today!

Why join InspectionNews? Read the Testimonials

Looking for Education? We recommend Casey, O'Malley and Associates
Home and Commercial Inspection Education

If you have any problems with the registration process or your account login, please contact us.

Reply
 
LinkBack Thread Tools Search this Thread
  #1 (permalink)  
Old 04-23-2008, 01:12 PM
Wendell Swedberg Wendell Swedberg is offline
Member
 
Join Date: Dec 2007
Location: phoenix
Posts: 50
Conductor Ampacity
ICC test question:

Number 12 AWG THHN , copper conductors that are located in the attic and are part of the NM cable. The ambient temperature around the conductors will be 110F. The terminal devices are not rated for more than 60degrees C......What is the conductor ampacity for this condition?

A) 20
B) 26
C) 30
D) 35

I get 30 amps from table 3605.1.....the answer is B, 26 amps...what gives?

Thanks as always for your help.

Wen
Reply With Quote
Home Inspector Essentials. The BEST prices for inspection tools.
  #2 (permalink)  
Old 04-23-2008, 01:50 PM
Bob White's Avatar
Bob White Bob White is offline
Member
 
Join Date: Mar 2007
Location: Cartersville, GA
Posts: 82
Re: Conductor Ampacity
Quote:
Originally Posted by Wendell Swedberg View Post
ICC test question:

Number 12 AWG THHN , copper conductors that are located in the attic and are part of the NM cable. The ambient temperature around the conductors will be 110F. The terminal devices are not rated for more than 60degrees C......What is the conductor ampacity for this condition?

A) 20
B) 26
C) 30
D) 35

I get 30 amps from table 3605.1.....the answer is B, 26 amps...what gives?

Thanks as always for your help.

Wen
Section E3605.2 sez that for ambient temperatures other than 30 degrees C (86 deg. F), mutiply your table 3605.1 allowable ampacity by th correction factor in table 3605.2 (0.87).

30 * 0.87 = 26.1 ......
__________________
Bob White

backstripe.wordpress.com
Reply With Quote
  #3 (permalink)  
Old 04-23-2008, 02:32 PM
Gunnar Alquist's Avatar
Gunnar Alquist Gunnar Alquist is offline
Member
 
Join Date: Mar 2007
Location: Santa Rosa, CA
Posts: 1,201
Re: Conductor Ampacity
If I remember correctly, there is a line in the NEC that states that #14 cannot exceed 15 amps and #12 cannot exceed 20 amps. Even though the tables indicate otherwise. I never understood what that was all about.
__________________
We have enough youth, how about a fountain of Smart?
Reply With Quote
  #4 (permalink)  
Old 04-23-2008, 02:48 PM
Michael Larson's Avatar
Michael Larson Michael Larson is offline
Member
 
Join Date: Mar 2007
Location: Hudson, WI
Posts: 642
Re: Conductor Ampacity
Quote:
Originally Posted by Gunnar Alquist View Post
If I remember correctly, there is a line in the NEC that states that #14 cannot exceed 15 amps and #12 cannot exceed 20 amps. Even though the tables indicate otherwise. I never understood what that was all about.
That is true for residential. I don't have the code reference handy.
Reply With Quote
  #5 (permalink)  
Old 04-23-2008, 04:20 PM
Jerry Peck's Avatar
Jerry Peck Jerry Peck is online now
Member
 
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 14,293
Re: Conductor Ampacity
Quote:
Originally Posted by Gunnar Alquist View Post
If I remember correctly, there is a line in the NEC that states that #14 cannot exceed 15 amps and #12 cannot exceed 20 amps. Even though the tables indicate otherwise. I never understood what that was all about.
Gunnar,

Wendell asked, and Bob correctly gave, the ampacity rating of the conductor in that condition.

You are referring to the maximum allowable overcurrent protection allowed, and the ampacity of the conductor in all derated conditions must exceed that for that overcurrent protection to be used.

Thus, for the question, Bob is correct, and, for overcurrent protection of that conductor in that condition, you are correct.

It is not separated 'residential' or 'non-residential', that applies to all installations.
__________________
Jerry Peck, Construction / Litigation Consultant
Construction Litigation Consultants, LLC ( www.ConstructionLitigationConsultants.com )
www.AskCodeMan.com
Reply With Quote
  #6 (permalink)  
Old 04-23-2008, 05:40 PM
Michael Larson's Avatar
Michael Larson Michael Larson is offline
Member
 
Join Date: Mar 2007
Location: Hudson, WI
Posts: 642
Re: Conductor Ampacity
My error. I was thinking of overcurret protection not circuit ampacity.


Reply With Quote
  #7 (permalink)  
Old 04-23-2008, 07:14 PM
Gunnar Alquist's Avatar
Gunnar Alquist Gunnar Alquist is offline
Member
 
Join Date: Mar 2007
Location: Santa Rosa, CA
Posts: 1,201
Re: Conductor Ampacity
JP,

Um... right. I knew that.

This would be why I am a home inspector and not a "code inspector". Guess I am not going to be taking the ICC exam any time soon.
__________________
We have enough youth, how about a fountain of Smart?
Reply With Quote
United Infrared
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
grounding electrode conductor Jerome W. Young Electrical Systems: Home Inspection and Commercial Inspection 4 04-16-2008 12:59 PM
Service Ampacity Matthew Barnicle Electrical Systems: Home Inspection and Commercial Inspection 6 03-14-2008 08:13 PM
Conductor protection Mike Schulz Electrical Systems: Home Inspection and Commercial Inspection 10 02-19-2008 03:13 PM
Conductor bundles dan orourke Electrical Systems: Home Inspection and Commercial Inspection 3 10-19-2007 12:37 PM
Conductor markings dan orourke Electrical Systems: Home Inspection and Commercial Inspection 4 07-15-2007 06:56 PM

Alabama | Alaska | Arizona | Atlanta | Aurora | Austin | Baltimore | Boston | California | Cambridge | Cape Coral | Chandler | Charlotte | Chicago | Cincinnati | Clarksville | Cleveland | Colorado | Columbus | Connecticut | Dallas | Delaware | Denver | Detroit | Durham | El Paso | Eugene | Florida | Fort Worth | Fresno | Georgia | Gilbert | Hawaii | Henderson | Houston | Huntsville | Idaho | Illinois | Indiana | Indianapolis | Irvine | Jacksonville | Joliet | Kansas City | Knoxville | Lancaster | Las Vegas | Los Angeles | Louisiana | Louisville | Maine | Maryland | Massachusetts | Memphis | Mesa | Miami | Michigan | Milwaukee | Minneapolis | Minnesota | Miramar | Mississippi | Missouri | Montana | Nashville | Nebraska | Nevada | New Hampshire | New Jersey | New Mexico | New York | North Carolina | North Dakota | Oakland | Ohio | Oklahoma | Omaha | Ontario | Orange | Oregon | Orlando | Pennsylvania | Philadelphia | Phoenix | Pittsburgh | Plano | Portland | Port StLucie | Raleigh | Rhode Island | Roseville | Sacramento | Salem | San Antonio | San Diego | San Francisco | San Jose | Scottsdale | Seattle | Sioux falls | South Carolina | South Dakota | St Louis | Tampa | Tennessee | Texas | Thornton | Toledo | Tucson | Tulsa | Utah | Vancouver | Vermont | Virginia | West Virginia | Wichita | Wisconsin | Wyoming | Cost To Repair

All times are GMT -7. The time now is 08:50 PM.


Design by Vjacheslav Trushkin.
Powered by vBulletin® Version 3.6.5
Copyright ©2000 - 2009, Jelsoft Enterprises Ltd.
Search Engine Optimization by vBSEO 3.0.0 RC8
vB.Sponsors
All Rights Reserved. Hann Tech Marketing Link / InspectionNews.com / InspectionNews.net - No part of InspectionNews.net may be reproduced in any way, or by any means, without the prior written permission of InspectionNews.net. Use of any index or listing Software for the purpose of constructing a mailing list, creating promotional materials or producing a printed or electronic catalog of any kind is expressly forbidden without the prior written permission of InspectionNews.net - All text, graphics and design on InspectionNews.net is copyright by Hann Tech Marketing Links.
Ad Management by RedTyger