InspectionNews - Home Inspection



Registration is FREE!... and will get rid of this top message

Welcome to InspectionNews.net.

You are currently viewing InspectionNews as a guest which gives you limited access to view some discussions but none of the pictures.

There are over 9,970 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, post new topics or reply to others, communicate privately with other members, respond to polls, upload content and access many other special features.

Registration is FREE for you because the sponsors pay your way. Please visit the sponsors often and let them know that you found them on InspectionNews!

Registration is FREE, fast and easy so please, join InspectionNews today!

Why join InspectionNews? Read the Testimonials

Looking for Education? We recommend Casey, O'Malley and Associates
Home and Commercial Inspection Education

If you have any problems with the registration process or your account login, please contact us.

Reply
 
LinkBack Thread Tools Search this Thread
  #1 (permalink)  
Old 04-29-2008, 06:08 PM
Wendell Swedberg Wendell Swedberg is offline
Member
 
Join Date: Dec 2007
Location: phoenix
Posts: 50
single grounding rod
ICC practice exam question:

If the system is grounded with a single ground rod, what is the maximum size copper required for the grounding electrode conductor regardless of the size of the electrical service?

a) #8
b) #6
c) #4
d) 3/0

I say #6 , but the answer is #4.

thanks as always for your help!
Reply With Quote
F.I.R.E. provides fireplace education, consulting services, fire investigation and litigation support across the United States.
  #2 (permalink)  
Old 04-29-2008, 06:51 PM
John Arnold John Arnold is offline
Member
 
Join Date: Mar 2007
Location: Philadelphia PA
Posts: 2,028
Re: single grounding rod
Quote:
Originally Posted by Wendell Swedberg View Post
ICC practice exam question:

If the system is grounded with a single ground rod, what is the maximum size copper required for the grounding electrode conductor regardless of the size of the electrical service?

a) #8
b) #6
c) #4
d) 3/0

I say #6 , but the answer is #4.

thanks as always for your help!
You mean minimum size, right?
Reply With Quote
  #3 (permalink)  
Old 04-29-2008, 09:02 PM
Wendell Swedberg Wendell Swedberg is offline
Member
 
Join Date: Dec 2007
Location: phoenix
Posts: 50
Re: single grounding rod
no, the question does say maximum.....
Reply With Quote
  #4 (permalink)  
Old 04-29-2008, 09:04 PM
Jerry Peck's Avatar
Jerry Peck Jerry Peck is online now
Member
 
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 14,293
Re: single grounding rod
Quote:
Originally Posted by John Arnold View Post
You mean minimum size, right?
John,

Maximum "required" in no way implies "maximum allowed".
__________________
Jerry Peck, Construction / Litigation Consultant
Construction Litigation Consultants, LLC ( www.ConstructionLitigationConsultants.com )
www.AskCodeMan.com
Reply With Quote
  #5 (permalink)  
Old 04-29-2008, 09:51 PM
Jerry Peck's Avatar
Jerry Peck Jerry Peck is online now
Member
 
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 14,293
Re: single grounding rod
Wendell,

Reading Table E3503.1 and notes 'a' and 'd', it does appear that 6 AWG copper is the "maximum size copper required" when the "system is grounded with a single ground rod".

What confuses things is that note 'd' states "Where the sole grounding electrode system is a ground or pipe as covered in Section E3508.2 ... "

And E3508.2 states: (which does not apply to "the sole grounding electrode system is a ground or pipe" as no bonding jumper is needed)
- E3508.2 Bonding jumper.
The bonding jumper(s) used to connect the grounding electrodes together to form the grounding electrode system shall be installed in accordance with Sections E3510.2, and E3510.3, shall be sized in accordance with Section E3503.4, and shall be connected in the manner specified in Section E3511.1.

This jumps from 'a grounding electrode conductor to a single ground rod' (singular) to 'a bonding jumper used to connect grounding electrodes together' (plural).

I don't see how that applies?????

That also refers you back to E3503.4:
- E3503.4 Grounding electrode conductor size.
The grounding electrode conductors shall be sized based on the size of the service entrance conductors as required in Table E3503.1.


Which is back to where we started.

It's almost like they did not mean to use the word "copper" in there, in which case (changing the word "copper" to "conductor")

'If the system is grounded with a single ground rod, what is the maximum size conductor required for the grounding electrode conductor regardless of the size of the electrical service?'

In that case, the answer would be #4.

Maybe I need to read that through again in the morning?
__________________
Jerry Peck, Construction / Litigation Consultant
Construction Litigation Consultants, LLC ( www.ConstructionLitigationConsultants.com )
www.AskCodeMan.com
Reply With Quote
  #6 (permalink)  
Old 04-30-2008, 06:41 AM
Wendell Swedberg Wendell Swedberg is offline
Member
 
Join Date: Dec 2007
Location: phoenix
Posts: 50
Re: single grounding rod
thanks, Jerry....there are just soooo many errors in the ICC practice exam questions and workbooks.....but they are still usefull materials , excericises to go through.
Reply With Quote
Are inspection referrals from past clients important to you?
If so, click here to get even more referrals!
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Circuit tester and grounding rod M Kelekci Electrical Systems: Home Inspection and Commercial Inspection 44 07-24-2009 06:55 PM
grounding electrode conductor Jerome W. Young Electrical Systems: Home Inspection and Commercial Inspection 4 04-16-2008 12:59 PM
Telephone equipment grounding fritzkelly Electrical Systems: Home Inspection and Commercial Inspection 1 04-02-2008 06:56 PM
Grounding to polybutylene Paul Kondzich Electrical Systems: Home Inspection and Commercial Inspection 11 03-07-2008 05:55 AM
Metal conduit grounding Mark Muehleisen Electrical Systems: Home Inspection and Commercial Inspection 3 06-09-2007 04:28 PM

Alabama | Alaska | Arizona | Atlanta | Aurora | Austin | Baltimore | Boston | California | Cambridge | Cape Coral | Chandler | Charlotte | Chicago | Cincinnati | Clarksville | Cleveland | Colorado | Columbus | Connecticut | Dallas | Delaware | Denver | Detroit | Durham | El Paso | Eugene | Florida | Fort Worth | Fresno | Georgia | Gilbert | Hawaii | Henderson | Houston | Huntsville | Idaho | Illinois | Indiana | Indianapolis | Irvine | Jacksonville | Joliet | Kansas City | Knoxville | Lancaster | Las Vegas | Los Angeles | Louisiana | Louisville | Maine | Maryland | Massachusetts | Memphis | Mesa | Miami | Michigan | Milwaukee | Minneapolis | Minnesota | Miramar | Mississippi | Missouri | Montana | Nashville | Nebraska | Nevada | New Hampshire | New Jersey | New Mexico | New York | North Carolina | North Dakota | Oakland | Ohio | Oklahoma | Omaha | Ontario | Orange | Oregon | Orlando | Pennsylvania | Philadelphia | Phoenix | Pittsburgh | Plano | Portland | Port StLucie | Raleigh | Rhode Island | Roseville | Sacramento | Salem | San Antonio | San Diego | San Francisco | San Jose | Scottsdale | Seattle | Sioux falls | South Carolina | South Dakota | St Louis | Tampa | Tennessee | Texas | Thornton | Toledo | Tucson | Tulsa | Utah | Vancouver | Vermont | Virginia | West Virginia | Wichita | Wisconsin | Wyoming | Cost To Repair

All times are GMT -7. The time now is 09:02 PM.


Design by Vjacheslav Trushkin.
Powered by vBulletin® Version 3.6.5
Copyright ©2000 - 2009, Jelsoft Enterprises Ltd.
Search Engine Optimization by vBSEO 3.0.0 RC8
vB.Sponsors
All Rights Reserved. Hann Tech Marketing Link / InspectionNews.com / InspectionNews.net - No part of InspectionNews.net may be reproduced in any way, or by any means, without the prior written permission of InspectionNews.net. Use of any index or listing Software for the purpose of constructing a mailing list, creating promotional materials or producing a printed or electronic catalog of any kind is expressly forbidden without the prior written permission of InspectionNews.net - All text, graphics and design on InspectionNews.net is copyright by Hann Tech Marketing Links.
Ad Management by RedTyger