You are currently viewing InspectionNews as a guest which gives you limited access to view most discussions but not pictures. There are over 4,500 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, have access to post topics, communicate privately with other members, respond to polls, upload content and access many other special features. Registration is fast and simple so please, join InspectionNews today!
If you have any problems with the registration process or your account login, please contact us.
Why join InspectionNews? Read the Testimonials
|
|

05-08-2008, 06:50 PM
|
|
Member
|
|
Join Date: Mar 2007
Posts: 21
|
|
|
Aluminum wiring with AFCI breakers
Inspected this house today and the seller has had the sub panel (15 and 20 amp circuits) replaced and the new panel now has every circuit on AFCI breakers. House is wired with aluminum wire. Will this panel be protecting all aluminum circuits throughout the house properly? I have never seen this before.
Also, some of the older receptacles were not CO/ALR and the aluminum wires have been pigtailed with copper using lavender wire connectors. I now these connectors are not quite safe and other type of connectors are recommended. What would be the best way to report on this?
Thank You
|
|

05-08-2008, 06:56 PM
|
|
Member
|
|
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 5,107
|
|
|
Re: Aluminum wiring with AFCI breakers
That is one of the original intended uses for AFCI breakers.
__________________
Jerry Peck
Construction Consultant
Ormond Beach, Florida
|
|

05-09-2008, 05:33 PM
|
|
Member
|
|
Join Date: Mar 2007
Location: Tampa, Fl
Posts: 76
|
|
|
Re: Aluminum wiring with AFCI breakers
Sounds like that is about the best they can do if they are keeping the original aluminum branch circuits. Don't know much about the lavender connectors but I believe they are designed for this purpose, no?
|
|

05-09-2008, 07:33 PM
|
|
Member
|
|
Join Date: May 2007
Location: NC
Posts: 318
|
|
|
Re: Aluminum wiring with AFCI breakers
Originally Posted by Jerry Peck
That is one of the original intended uses for AFCI breakers.
Jerry...
Where can I find info on that? I did four townhouses in the past two weeks that had aluminum wiring. I would love to be able to give this option as a repair. I advise against the pigtail fix.
|
|

05-09-2008, 07:42 PM
|
|
Member
|
|
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 5,107
|
|
|
Re: Aluminum wiring with AFCI breakers
Check on the CPSC site, they should have something on there about AFCIs and the reason they came about, I think I read something on their site about that.
__________________
Jerry Peck
Construction Consultant
Ormond Beach, Florida
|
|

05-09-2008, 07:55 PM
|
|
Member
|
|
Join Date: May 2007
Location: NC
Posts: 318
|
|
|
Re: Aluminum wiring with AFCI breakers
Originally Posted by Jerry Peck
That is one of the original intended uses for AFCI breakers.
Thanks...I've haven't been there is a while so I'll check for new info. I'll let you know what I find.
|
|

05-09-2008, 07:57 PM
|
|
Member
|
|
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 5,107
|
|
|
Re: Aluminum wiring with AFCI breakers
Originally Posted by James Duffin
Thanks...I've haven't been there is a while so I'll check for new info. I'll let you know what I find.
James,
I believe it was a couple of years ago or so.
__________________
Jerry Peck
Construction Consultant
Ormond Beach, Florida
|
|

05-09-2008, 08:25 PM
|
|
Member
|
|
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 5,107
|
|
|
Re: Aluminum wiring with AFCI breakers
CPSC, ESFI Warn Consumers About Electrical Hazards In The Home "Inspect and Protect!" Campaign Encourages Homeowners to Safeguard Homes
(underlining is mine - maybe I just added 2+2+2 and got 6)
" This summer, CPSC and ESFI are encouraging homeowners to: 1) have an electrical inspection conducted for homes 40 years and older, for homes 10 years and older with major renovations or new appliances added, or that have been resold; 2) learn the potential hazards posed by aluminum wiring systems and contact CPSC if your home is among the two million built with aluminum wiring between the late 1960s and early 1970s; and 3) consider installing arc fault circuit interrupters in place of ordinary circuit breakers, especially if your home is over 40 years old. AFCIs are new technology designed to prevent electrical fires by sensing unseen electrical arcing. AFCIs are particularly important where wiring may have degraded with age."
http://www.cpsc.gov/LIBRARY/FOIA/FOI...FCImeeting.pdf
Slide on page 22 of 38, Enhanced Protection, Currently available AFCIs provide protection beyond standard breakers and fuses: aluminum wiring (then other things listed)
__________________
Jerry Peck
Construction Consultant
Ormond Beach, Florida
|
|
| Thread Tools |
Search this Thread |
|
|
|
Posting Rules
|
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts
HTML code is Off
|
|
|
All times are GMT -7. The time now is 08:56 AM.
| | |
|
All Rights Reserved. Hann Tech Marketing Link / InspectionNews.com / InspectionNews.net - No part of InspectionNews.net may be reproduced in any way, or by any means, without the prior written permission of InspectionNews.net. Use of any index or listing Software for the purpose of constructing a mailing list, creating promotional materials or producing a printed or electronic catalog of any kind is expressly forbidden without the prior written permission of InspectionNews.net - All text, graphics and design on InspectionNews.net is copyright by Hann Tech Marketing Links.
Ad Management by
RedTyger