Originally Posted by
Ross Neag
On a condo panel that has NO MAIN, is it service or a subpanel
Neither.
It is not the service panel, nor is it a "subpanel" as there is no such thing.
It is a "distribution panel", or, if it is easier to remember, it is "not service equipment".
Main service closet was unavailable for entrance.
Why? Locked? No one knew where it was?
Reason asking is ground and neutral were on same bus.
Being as it is "not service equipment", the neutral is to be isolated from ground.
How do I *know* it is "not service equipment"? Because it is *one building* and *one building* does not allow for each of 50 units to have "service equipment" in them.