InspectionNews - Home Inspection



Registration is FREE!... and will get rid of this top message

Welcome to InspectionNews.net.

You are currently viewing InspectionNews as a guest which gives you limited access to view some discussions but none of the pictures.

There are over 9,970 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, post new topics or reply to others, communicate privately with other members, respond to polls, upload content and access many other special features.

Registration is FREE for you because the sponsors pay your way. Please visit the sponsors often and let them know that you found them on InspectionNews!

Registration is FREE, fast and easy so please, join InspectionNews today!

Why join InspectionNews? Read the Testimonials

Looking for Education? We recommend Casey, O'Malley and Associates
Home and Commercial Inspection Education

If you have any problems with the registration process or your account login, please contact us.

Reply
 
LinkBack Thread Tools Search this Thread
  #1 (permalink)  
Old 03-27-2009, 10:00 PM
Terry Sandmeier's Avatar
Terry Sandmeier Terry Sandmeier is offline
Member
 
Join Date: Feb 2008
Location: Buena Vista, Colorado
Posts: 35
Mandatory CO detectors in Colorado
As of 3/25/09 HB 1091 requiring CO detectors in all houses before they are listed in for sale has been signed by the GOV. Ritter and will be in effect starting 8/1/09.

1) NOTWITHSTANDING ANY OTHER PROVISION OF LAW, EACH
11 EXISTING SINGLE-FAMILY DWELLING OFFERED FOR SALE OR TRANSFER ON
12 OR AFTER JULY 1, 2009, THAT HAS A FUEL-BURNING HEATER OR
13 APPLIANCE, A FIREPLACE, OR AN ATTACHED GARAGE SHALL HAVE AN
14 OPERATIONAL CARBON MONOXIDE ALARM INSTALLED WITHIN TEN FEET OF
15 THE ENTRANCE TO EACH ROOM LAWFULLY USED FOR SLEEPING PURPOSES.

There is also a provision that any rental properties that change tenants after this period must comply with this law.

This has really gotten attention after a family of four was found dead in there multi-million dollar home in Aspen and a 23 year old DU student was killed by Carbon Monoxide. In both of these incidences there was not a CO detector in the house.

In the winter time in Colorado 83% of homes are heated by gas of solid fuel appliances and in the winter time there is obviously increased use for heating.

I believe this is a great requirement for the safety of any home owner. I have always recommended CO and smoke and fire alarms to be upgraded and installed accordingly. This will get a few more people motivated to safety in the house.
Reply With Quote
Home inspection - The Cost Of Business.
  #2 (permalink)  
Old 04-03-2009, 08:16 PM
Harry Settle Harry Settle is offline
Member
 
Join Date: Apr 2009
Location: Bemidji, Minnesota
Posts: 15
Re: Mandatory CO detectors in Colorado
They went mandatory in Minnesota last year, now they are all hanging from the ceilings in pieces, just like a lot of the smoke detectors.
Reply With Quote
  #3 (permalink)  
Old 04-03-2009, 08:28 PM
Billy Stephens's Avatar
Billy Stephens Billy Stephens is online now
Member
 
Join Date: Aug 2007
Location: Memphis TN.
Posts: 2,278
Re: Mandatory CO detectors in Colorado
Quote:
Originally Posted by Terry Sandmeier;78575[SIZE=3
]

[/size] In the winter time in Colorado 83% of homes are heated by gas of solid fuel appliances and in the winter time there is obviously increased use for heating.
.
.
What kind of fuel and or heater ?
.
__________________
It Might have Choked Artie But it ain't gone'a choke Stymie!
Billy J. Stephens HI Service
Memphis TN.
Reply With Quote
  #4 (permalink)  
Old 04-03-2009, 08:47 PM
Terry Sandmeier's Avatar
Terry Sandmeier Terry Sandmeier is offline
Member
 
Join Date: Feb 2008
Location: Buena Vista, Colorado
Posts: 35
Re: Mandatory CO detectors in Colorado
Quote:
What kind of fuel and or heater ?
Billy:
I had re read my post and I mis spelled - or - in the sentence, In the winter time in Colorado 83% of homes are heated by gas of solid fuel appliances and in the winter time there is obviously increased use for heating. It should read In the winter time in Colorado 83% of homes are heated by gas or solid fuel appliances and in the winter time there is obviously increased use for heating.

Does that clear it up for you?
Reply With Quote
  #5 (permalink)  
Old 04-03-2009, 09:02 PM
Billy Stephens's Avatar
Billy Stephens Billy Stephens is online now
Member
 
Join Date: Aug 2007
Location: Memphis TN.
Posts: 2,278
Re: Mandatory CO detectors in Colorado
Quote:
Originally Posted by Terry Sandmeier View Post
Billy:
I had re read my post and I mis spelled - or - in the sentence, In the winter time in Colorado 83% of homes are heated by gas of solid fuel appliances and in the winter time there is obviously increased use for heating. It should read In the winter time in Colorado 83% of homes are heated by gas or solid fuel appliances and in the winter time there is obviously increased use for heating.

Does that clear it up for you?
.
Yep.
.
__________________
It Might have Choked Artie But it ain't gone'a choke Stymie!
Billy J. Stephens HI Service
Memphis TN.
Reply With Quote
  #6 (permalink)  
Old 09-09-2009, 10:15 PM
Bruce Breedlove's Avatar
Bruce Breedlove Bruce Breedlove is offline
Member
 
Join Date: Mar 2007
Location: Colorado Springs, CO
Posts: 814
Re: Mandatory CO detectors in Colorado
Still no word on who is responsible to ensure that homes sold or rented in Colorado have operational CO detectors. It certainly is not my job. Maybe it is the Realtor's job. (They get paid more than I do.)

But that begs the question: What about houses that are sold (or rented) without a home inspector or real estate agent?
__________________
"Baseball is like church. Many attend but few understand." Leo Durocher
Bruce Breedlove
www.avaloninspection.com
Reply With Quote
  #7 (permalink)  
Old 09-09-2009, 10:28 PM
Rick Hurst's Avatar
Rick Hurst Rick Hurst is offline
Member
 
Join Date: Oct 2003
Location: Rockwall Texas
Posts: 3,655
Re: Mandatory CO detectors in Colorado
Please no one call TREC and tell them about this!

rick
Reply With Quote
  #8 (permalink)  
Old 09-09-2009, 11:40 PM
Ron Bibler's Avatar
Ron Bibler Ron Bibler is online now
Member
 
Join Date: Mar 2008
Location: Healdsburg Ca
Posts: 1,947
Re: Mandatory CO detectors in Colorado
Did we not have a post some time back on how these things did not work very well. or was it that they were to low on the wall?

Ive had one of them things in my home for the past 12 years.

dang thing has never gone of ?

Best

Ron
Reply With Quote
  #9 (permalink)  
Old 09-09-2009, 11:51 PM
Bruce Breedlove's Avatar
Bruce Breedlove Bruce Breedlove is offline
Member
 
Join Date: Mar 2007
Location: Colorado Springs, CO
Posts: 814
Re: Mandatory CO detectors in Colorado
Quote:
Originally Posted by Ron Bibler View Post
Did we not have a post some time back on how these things did not work very well. or was it that they were to low on the wall?
CO is lighter than air. Plus it is usually created when something is burned so CO is often found in warmer air which tends to rise. So CO will typically collect near the ceiling.

For those reasons the best location for a CO detector is either on the ceiling or high on a wall, not below knee level at an electrical outlet. By the time the CO accumulates enough for a detector near the floor to detect it it may be too late for those that breathe the air above the electrical outlets.
__________________
"Baseball is like church. Many attend but few understand." Leo Durocher
Bruce Breedlove
www.avaloninspection.com

Last edited by Bruce Breedlove : 09-10-2009 at 12:09 AM. Reason: spelling
Reply With Quote
  #10 (permalink)  
Old 09-19-2009, 08:19 AM
DavidR's Avatar
DavidR DavidR is offline
Member
 
Join Date: May 2007
Location: Frankfort, KY
Posts: 281
Re: Mandatory CO detectors in Colorado
Quote:
Originally Posted by Bruce Breedlove View Post
CO is lighter than air. Plus it is usually created when something is burned so CO is often found in warmer air which tends to rise. So CO will typically collect near the ceiling.

For those reasons the best location for a CO detector is either on the ceiling or high on a wall, not below knee level at an electrical outlet. By the time the CO accumulates enough for a detector near the floor to detect it it may be too late for those that breathe the air above the electrical outlets.
You're dead on Bruce.

Any of you guys close to Denver I will be there in two weeks teaching a three day certification course on this very topic.

Would be nice to put some faces to some names.
__________________
Measured Performance more than just a buzzword
Reply With Quote
  #11 (permalink)  
Old 09-22-2009, 08:47 PM
Bruce Breedlove's Avatar
Bruce Breedlove Bruce Breedlove is offline
Member
 
Join Date: Mar 2007
Location: Colorado Springs, CO
Posts: 814
Re: Mandatory CO detectors in Colorado
David,

Drop me a line with some info on your course. Not sure if I will be able to attend but you never know.

Bruce
__________________
"Baseball is like church. Many attend but few understand." Leo Durocher
Bruce Breedlove
www.avaloninspection.com
Reply With Quote
  #12 (permalink)  
Old 09-23-2009, 02:13 PM
DavidR's Avatar
DavidR DavidR is offline
Member
 
Join Date: May 2007
Location: Frankfort, KY
Posts: 281
Re: Mandatory CO detectors in Colorado
Quote:
Originally Posted by Bruce Breedlove View Post
David,

Drop me a line with some info on your course. Not sure if I will be able to attend but you never know.

Bruce
You've got a PM Bruce.
__________________
Measured Performance more than just a buzzword
Reply With Quote
  #13 (permalink)  
Old 09-23-2009, 04:04 PM
Bob Harper's Avatar
Bob Harper Bob Harper is online now
Member
 
Join Date: Mar 2007
Location: Near Philly, Pa.
Posts: 815
NCI course
You won't be sorry you took this course. A TON of eye opening info. and David really knows his stuff. I highly recommend it. Being a great HVAC tech, he can relate real world applications and experience to it. He also practices what he preaches.
Bob
__________________
Keep the fire in the fireplace.
Reply With Quote
  #14 (permalink)  
Old 09-23-2009, 05:03 PM
Ted Menelly Ted Menelly is offline
Member
 
Join Date: Mar 2007
Location: Fort Worth, Texas
Posts: 3,075
Re: Mandatory CO detectors in Colorado
Quote:
Originally Posted by Bruce Breedlove View Post
Still no word on who is responsible to ensure that homes sold or rented in Colorado have operational CO detectors. It certainly is not my job. Maybe it is the Realtor's job. (They get paid more than I do.)

But that begs the question: What about houses that are sold (or rented) without a home inspector or real estate agent?

I would say that if the Gov put it into law then you should make it one of your safety write ups. I have been writing detectors missing or not working for ever. Smoke, heat CO what ever should be used for the particular home.

I know Rick had the big Grinning face on his post but we here in Texas write detectors up all the time. It should be part of any home inspectors findings.

Now if there is an exact spot in any home such as 2 feet from here or no further than 5 feet from there is a whole nother topic of convo.

At the least smoke detctors in every sleeping room and outside those sleeping areas and CO detectors in any area that has a furnace, water heater etc should be the minimum write up.
__________________
Ted Menelly
Castle Home Inspection Services
www.inspectmycastle.com
Reply With Quote
  #15 (permalink)  
Old 09-24-2009, 03:52 PM
DavidR's Avatar
DavidR DavidR is offline
Member
 
Join Date: May 2007
Location: Frankfort, KY
Posts: 281
Re: NCI course
Quote:
Originally Posted by Bob Harper View Post
You won't be sorry you took this course. A TON of eye opening info. and David really knows his stuff. I highly recommend it. Being a great HVAC tech, he can relate real world applications and experience to it. He also practices what he preaches.
Bob
Thanks for the vote of confidence Bob!

Saw some things in Wyoming last week that I would have previously said were impossible.

1.7% O2 stable and venting.
__________________
Measured Performance more than just a buzzword
Reply With Quote
IC Home Inspection Report Writing
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Buffalo in Colorado Paul Kondzich General Chit Chat: Home Inspectors & Commercial Inspectors 3 07-02-2008 03:23 PM
Hello From Colorado Calvin Watson Introductions By New Members 1 02-10-2008 08:34 AM
Revisiting Carbon Monoxide Detectors Victor DaGraca Inspection News From Around The Net 0 01-18-2008 04:38 PM
How often should smoke detectors be replaced? Jerry Peck Electrical Systems: Home Inspection and Commercial Inspection 15 08-15-2007 07:00 PM
smoke detectors wayne soper Building Interior: Home Inspection and Commercial Inspection 4 04-12-2007 01:58 PM

Alabama | Alaska | Arizona | Atlanta | Aurora | Austin | Baltimore | Boston | California | Cambridge | Cape Coral | Chandler | Charlotte | Chicago | Cincinnati | Clarksville | Cleveland | Colorado | Columbus | Connecticut | Dallas | Delaware | Denver | Detroit | Durham | El Paso | Eugene | Florida | Fort Worth | Fresno | Georgia | Gilbert | Hawaii | Henderson | Houston | Huntsville | Idaho | Illinois | Indiana | Indianapolis | Irvine | Jacksonville | Joliet | Kansas City | Knoxville | Lancaster | Las Vegas | Los Angeles | Louisiana | Louisville | Maine | Maryland | Massachusetts | Memphis | Mesa | Miami | Michigan | Milwaukee | Minneapolis | Minnesota | Miramar | Mississippi | Missouri | Montana | Nashville | Nebraska | Nevada | New Hampshire | New Jersey | New Mexico | New York | North Carolina | North Dakota | Oakland | Ohio | Oklahoma | Omaha | Ontario | Orange | Oregon | Orlando | Pennsylvania | Philadelphia | Phoenix | Pittsburgh | Plano | Portland | Port StLucie | Raleigh | Rhode Island | Roseville | Sacramento | Salem | San Antonio | San Diego | San Francisco | San Jose | Scottsdale | Seattle | Sioux falls | South Carolina | South Dakota | St Louis | Tampa | Tennessee | Texas | Thornton | Toledo | Tucson | Tulsa | Utah | Vancouver | Vermont | Virginia | West Virginia | Wichita | Wisconsin | Wyoming | Cost To Repair

All times are GMT -7. The time now is 03:10 PM.


Design by Vjacheslav Trushkin.
Powered by vBulletin® Version 3.6.5
Copyright ©2000 - 2009, Jelsoft Enterprises Ltd.
Search Engine Optimization by vBSEO 3.0.0 RC8
vB.Sponsors
All Rights Reserved. Hann Tech Marketing Link / InspectionNews.com / InspectionNews.net - No part of InspectionNews.net may be reproduced in any way, or by any means, without the prior written permission of InspectionNews.net. Use of any index or listing Software for the purpose of constructing a mailing list, creating promotional materials or producing a printed or electronic catalog of any kind is expressly forbidden without the prior written permission of InspectionNews.net - All text, graphics and design on InspectionNews.net is copyright by Hann Tech Marketing Links.
Ad Management by RedTyger