You are currently viewing InspectionNews as a guest which gives you limited access to view most discussions but not pictures. There are over 6,300 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, have access to post topics, communicate privately with other members, respond to polls, upload content and access many other special features. Registration is fast and simple so please, join InspectionNews today!
If you have any problems with the registration process or your account login, please contact us.
Why join InspectionNews? Read the Testimonials
|
|

12-11-2007, 04:03 PM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Chicago, IL
Posts: 1,155
|
|
|
Grading and drainage requirments
We always give advice about grading away from a structure “one inch per foot for the first ten feet” or the like, but I just realized that beyond common sense I don't have a cite for the requirement. Is in the IRC, or is it some sort of standard from civil engineering, or what?
Ditto for 6' on downspout discharge from structure.
|
|

12-11-2007, 04:40 PM
|
 |
Member
|
|
Join Date: Aug 2007
Location: Memphis TN.
Posts: 1,602
|
|
|
Re: Grading and drainage requirments
Michael,
I'll bite.
IRC 2003 R202 Definitions Grade Plane-------------------------Where the finished ground level slopes away from the exterior walls,----------------------------------------------.
Also: IRC 2003 R401.3 Drainage.----------------------------------The grade away from the foundation shall fall a minimum of 6 inches within the first 10 feet.
__________________
It Might have Choked Artie But it ain't gone'a choke Stymie!
Billy J. Stephens HI Service
Memphis TN.
Last edited by Billy Stephens : 12-11-2007 at 04:56 PM.
Reason: R401.3 added
|
|

12-11-2007, 06:18 PM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Chicago, IL
Posts: 1,155
|
|
|
Re: Grading and drainage requirments
Thanks.
Now, about the downspouts being 6' out...
|
|

12-11-2007, 06:23 PM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Chicago, IL
Posts: 1,155
|
|
|
Re: Grading and drainage requirments
Also, I've got this in my notes, but from where?
"The final grade should provide a minimum slope of one-half unit vertical in 12 units horizontal for a minimum of 6 feet from the home"
|
|

12-11-2007, 06:56 PM
|
 |
Member
|
|
Join Date: Aug 2007
Location: Memphis TN.
Posts: 1,602
|
|
|
Re: Grading and drainage requirments
Originally Posted by Michael Thomas
Also, I've got this in my notes, but from where?
"The final grade should provide a minimum slope of one-half unit vertical in 12 units horizontal for a minimum of 6 feet from the home"
IRC 2003 R202 Grade Plane
Gutters? Anyone? 6 ft Requirement. 
.
.
.
__________________
It Might have Choked Artie But it ain't gone'a choke Stymie!
Billy J. Stephens HI Service
Memphis TN.
|
|

12-11-2007, 07:13 PM
|
 |
Member
|
|
Join Date: Mar 2007
Location: San Mateo, CA
Posts: 1,103
|
|
|
Re: Grading and drainage requirments
This is what proper gutter extensions should look like. 
|
|

12-11-2007, 07:14 PM
|
|
Member
|
|
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 7,648
|
|
|
Re: Grading and drainage requirements
In Florida the gutter/downspout discharge is required to be at least 12 inches from the foundation wall/slab edge.
Don't know of anything in the IRC.
The purpose is to get the discharging water out past the termite treatment area.
|
|

12-11-2007, 07:15 PM
|
|
Member
|
|
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 7,648
|
|
|
Re: Grading and drainage requirements
|
|

12-11-2007, 07:50 PM
|
 |
Member
|
|
Join Date: Aug 2007
Location: Memphis TN.
Posts: 1,602
|
|
|
Re: Grading and drainage requirments
Originally Posted by Jerry McCarthy
This is what proper gutter extensions should look like. 
Jerry Mc.,
I hope you wrote up the Improper Clearance from the Ground on that front Siding. 
__________________
It Might have Choked Artie But it ain't gone'a choke Stymie!
Billy J. Stephens HI Service
Memphis TN.
|
|

12-12-2007, 05:49 AM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Succasunna NJ
Posts: 144
|
|
|
Re: Grading and drainage requirments
R801.3 (NJ edition)
Roof drainage. In areas where expansive or collapsible soils are known to exist, all dwellings shall have a controlled method of water disposal from roofs that will collect and discharge roof drainage to the ground surface at least 5 feet from foundation walls or to an approved drainage system.
Darren
New Jersey Home Inspection - About the House!
Last edited by Darren Miller : 12-12-2007 at 05:50 AM.
Reason: spelling
|
|

12-12-2007, 06:01 AM
|
|
Senior Member
|
|
Join Date: Mar 2007
Location: Nowhere, USA
Posts: 828
|
|
|
Re: Grading and drainage requirments
Michael:
The 6" drop in the first 10' out from the foundation perimeter is also a HUD requirement. Additionally, if the foundation is a slab-on-grade, it is a Post-Tensioning Institute requirement. And finally, if this is a new home covered by a warranty or one where the foundation has been repaired and is under warranty, the warranty validity is dependent upon the owner's adherence with this drainage provision.
Aaron
|
|

12-12-2007, 07:56 AM
|
 |
Member
|
|
Join Date: Oct 2003
Location: Rockwall Texas
Posts: 2,396
|
|
|
Re: Grading and drainage requirments
Aaron,
Your on the money about the home warranty. I had a PC customer who had filed a claim against the builder / and the home warranty for foundation movement.
As soon as the warranty people came out, they told her she had added those stackable stones around the shrub bed which obstructed the drainage, therefore the warranty was void. According to them, no changes should be made to the original grading whatsoever to keep such a warranty in place.
rick
|
|

12-12-2007, 08:16 AM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Duncanville, Tx
Posts: 1,086
|
|
|
Re: Grading and drainage requirments
Those same warranty folks will deny a claim if you add shrubs or plant trees. Again, these "Warranty" companies are in business to *make* money, not give it away. They will do what ever necessary to drop a claim.
Rich
__________________
"If con is the opposite of pro, is Congress the opposite of progress?"
Richard Rushing, HCRI
Duncanville, Tx.
|
|

12-12-2007, 09:41 AM
|
 |
Member
|
|
Join Date: Aug 2007
Location: Memphis TN.
Posts: 1,602
|
|
|
Re: Grading and drainage requirments
Originally Posted by Darren Miller
R801.3 (NJ edition)
Roof drainage. In areas where expansive or collapsible soils are known to exist, all dwellings shall have a controlled method of water disposal from roofs that will collect and discharge roof drainage to the ground surface at least 5 feet from foundation walls or to an approved drainage system.
Darren
New Jersey Home Inspection - About the House!
Bingo Thanks Darren,
Also in IRC 2003 R801.3
__________________
It Might have Choked Artie But it ain't gone'a choke Stymie!
Billy J. Stephens HI Service
Memphis TN.
|
|

12-12-2007, 01:59 PM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Santa Rosa, CA
Posts: 747
|
|
|
Re: Grading and drainage requirments
Jerry Mc,
Nice personal pic. Much more flattering than the last one. Of course, the same could be said about mine...
__________________
The apostrophe troll.
|
|
| Thread Tools |
Search this Thread |
|
|
|
Posting Rules
|
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts
HTML code is Off
|
|
|
| Thread |
Thread Starter |
Forum |
Replies |
Last Post |
| condensate pump drainage |
wayne soper |
Plumbing System: Home Inspection and Commercial Inspection |
5 |
03-10-2008 08:08 PM |
| Drainage under walkway |
Clay E White |
Exterior Systems: Home Inspection and Commercial Inspection |
3 |
09-23-2007 08:47 PM |
| Grading and drainage |
imported_John Smith |
Exterior Systems: Home Inspection and Commercial Inspection |
5 |
07-27-2007 06:49 PM |
| Drainage Advice Needed |
Phillip Joyner, Jr. |
Exterior Systems: Home Inspection and Commercial Inspection |
10 |
06-10-2007 05:17 PM |
| Loud gurlging noises - sink/tub drainage |
John Stephenson |
Plumbing System: Home Inspection and Commercial Inspection |
5 |
05-16-2007 09:57 PM |
All times are GMT -7. The time now is 04:28 PM.
| | |
|