Thread: Direct vent under a window....
-
09-18-2014, 02:28 PM #1
Direct vent under a window....
I know this was addressed before, but I just thought I would post this with a picture.
Our County inspectors have been "OK-ing" install like the following.
I flagged it with a comment that the county OK'ed it...
This looks so wrong to me...I would want to make the window non-functioning to be safe...but the county has been saying OK...
The install instructions say 12" (1 foot) is all that is required below a window that is operable, this looks to be right on that 12" line (Its two floors up so I couldn't easily measure it)
P9180009.jpg
Last edited by Bob Sisson; 09-18-2014 at 02:34 PM.
-
09-18-2014, 02:49 PM #2
Re: Direct vent under a window....
Well, the County is correct in OK'ing it if it's installed per spec.
You may not like it, but you could always contact the manufacturer and clarify their engineering.
Dom.
-
09-18-2014, 03:05 PM #3
Re: Direct vent under a window....
Bob,
Its customary to list where you are located geographically. It helps those of us in providing answers based on state rules/legislation, et ceteras ..
Thanks
-
09-18-2014, 04:15 PM #4
Re: Direct vent under a window....
Sorry... Montgomery County Maryland....
We also used to have lots of flueless fireplaces with burners deliberately set to be yellow & sooty so they looked nice while they dumped lots of water vapor and combustion byproducts into your home...