    Default Air Return within 10 ft of Firebox

    Is this acceptable ? Return is within 6 ft. of gas logs firebox (is the rule within 10 ft. for this type application) there are two returns, one at front of house and toward the back

    Similar Threads:
    Whole House Fan

  2. #2
    Join Date
    Mar 2007
    Location
    Plano, Texas
    Posts
    173

    Default Re: Air Return within 10 ft of Firebox

    M1602.2 Return Air Openings
    Return air openings for heating, ventilation and air conditioning systems shall comply with all of the following:

    1. Openings shall not be located less than 10 feet (3048 mm) measured in any direction from an open combustion chamber or draft hood of another appliance located in the same room or space.