Results 1 to 9 of 9
Thread: Traps and Sump pumps
-
01-08-2009, 05:37 AM #1
Traps and Sump pumps
House had two central a/c units- handlers side by side- both condensate lines were 3/4 pvc and connected with a T ...then run directly without trap to a sump pump below. Sump discharge line was one of the old high pressure copper lines
Can you use one pump to handle two units?
do you need a trap with a sump pump?
Similar Threads:
-
01-08-2009, 06:47 AM #2
-
01-08-2009, 06:51 AM #3
-
01-08-2009, 07:53 AM #4
Re: Traps and Sump pumps
The pipe size should have been a larger size from the T connection on.
From the 2004 Florida Building Code (underlining is mine)
- M1411.3.2 Drain pipe materials and sizes.
- - Components of the condensate disposal system shall be cast iron, galvanized steel, copper, polybutylene, polyethylene, ABS, CPVC or PVC pipe or tubing. All components shall be selected for the pressure and temperature rating of the installation. Condensate waste and drain line size shall be not less than ¾-inch (91 mm) internal diameter and shall not decrease in size from the drain pan connection to the place of condensate disposal. Where the drain pipes from more than one unit are manifolded together for condensate drainage, the pipe or tubing shall be sized in accordance with an approved method. All horizontal sections of drain piping shall be installed in uniform alignment at a uniform slope.
then run directly without trap to a sump pump below.do you need a trap with a sump pump?
Yes, the condensate lines need to be trapped at each unit in accordance with the manufacturers installation instructions (which will show a trap in the primary condensate line at each unit and a trap in the secondary condensate line at each unit)
Sump discharge line was one of the old high pressure copper linesCan you use one pump to handle two units?
Most condensate pumps are of the smaller versions, larger versions are made. If the tank for the condensate pump is too small, the motor would run more often than intended, also, larger units have larger motors capable of running more frequently.
Some condensate pumps are rated "continuous duty" and others are not.
The only true answer would be to call the manufacturer and give them the model number of the condensate pump and get a yes or no from them.
If it seems to be working, and it has been installed for a while, then it likely has the capacity to handle both, whether it is rated for it or not is a different issue.
The main thing I see with condensate pumps is they are typically placed in the return air under the unit, just exactly where you really want to place a petri dish with fungal growth in it!
Also, most come with a power cord with a molded on plug, which is promptly cut off ... and further use of that now damaged/altered cord is not allowed. Of course, though, the installers do not care, so they permanently wire it into the AHU.
Last edited by Jerry Peck; 01-08-2009 at 11:30 AM. Reason: deleted a random floating air borne "you" which landed in the post :-)
-
01-08-2009, 08:05 AM #5
Re: Traps and Sump pumps
JP: I believe his post said "sump" and not "condensate" pump.
-
01-08-2009, 08:12 AM #6
Re: Traps and Sump pumps
-
01-08-2009, 08:31 AM #7
-
01-08-2009, 08:37 AM #8
Re: Traps and Sump pumps
-
01-08-2009, 10:42 AM #9
Re: Traps and Sump pumps
yup meant pump
thanks!
Bookmarks