    Default oil tank vent pipe size

    Can someone remind me of the minimum size for the oil tank vent pipe?

    Similar Threads:
    Member Benefits1
    "There is no exception to the rule that every rule has an exception." -James Thurber, writer and cartoonist (1894-1961)
    www.ArnoldHomeInspections.com

  2. #2
    Jeff Remas's Avatar
    Jeff Remas Guest

    Default Re: oil tank vent pipe size

    1-1/4" per NFPA. They increased it to 2" then decreased it back to 1-1/4". If you start putting tanks in series then you may have to increase it is size depending on whether or not your areas has adopted the IFC or the NFPA. They differ in requirements.